Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

43

Set Up Your DeviceNet Network

Chapter 3

Follow these steps to use the Node Commissioning tool.

1.

Within RSNetWorx for DeviceNet software, choose Tools>Node
Commissioning.

2.

Click Browse on the Node Commissioning dialog box to select a device by
browsing the network.

You can browse through the SmartGuard USB port or the Ethernet/IP
port to reach the DeviceNet port.

3.

Select the DeviceNet network in the left panel.

4.

Select the device you want to commission in the right panel and click OK.

5.

Select the desired value if you want to change the communication rate of
the device.

6.

On the Node Commissioning dialog box, type the new address for the
device and click Apply.

A confirmation message tells you if the operation was successful.

IMPORTANT

The communication rate of the device will not update until the device is
power-cycled or reset.

IMPORTANT

To change the node address of a Safety device, you must first reset the
safety network number (SNN) to an uninitialized state by performing a
safety reset as described on page 45.