Chapter 7
Configure Your Controller for DeviceNet Communication
2.
Click the Safety Slave I/O tab.
3.
Click New.
4.
In the Edit Safety Slave I/O dialog box, click the I/O Type, either Safety
Slave Input or Safety Slave Output.
5.
To add status information for Safety Input types, check the appropriate
Status checkbox.
I/O Type
Safety Data Direction
Safety Slave Input
SmartGuard controller safety slave —> safety master
Safety Slave Output
Safety master —> SmartGuard controller safety slave
Tag Name
Data Size
Attribute Type
General Status
Byte
Non-safety
Local Input Status
Word
Safety
Local Output Status
Byte
Safety
Test Output/Muting Lamp Status
Byte
Non-safety