Chapter 2

Installing and Wiring the SmartGuard 600 Controller

Set the communication rate by using the DIP switch on the front of the
controller.

Figure 3 - Communication Rate Dip Switch

If you set other devices to autobaud, at least one device on the network must have
a communication rate established. If you set all devices on the network to
autobaud, they will not be able to establish a communication rate and will not
communicate with each other.

Ethernet Communication

We recommend connecting the module to the network via a 100 Mbps Ethernet
switch, which will help reduce collisions and lost packets and increase bandwidth.

The 1752-L24BBBE controller is shipped with BOOTP enabled for setting the
IP address. You can use any commercially available BOOTP server. If you do not
have BOOTP Server capabilities on your network, download the free Rockwell
Automation BOOTP server from http://www.rockwellautomation.com/
rockwellsoftware/download/.

To set the IP address by using the Rockwell Automation BOOTP utility, refer to
page 51.

The following table provides additional EtherNet/IP information.

DIP Switch Pin

Communication Rate

1

2

3

4

OFF

OFF

OFF

OFF

125 Kbps

ON

OFF

OFF

OFF

250 Kbps

OFF

ON

OFF

OFF

500 Kbps

ON

ON

OFF

OFF

Set by software

ON or OFF

ON or OFF

ON

OFF

Set by software

ON or OFF

ON or OFF

ON or OFF

ON

Automatic baud rate detection

IMPORTANT

If you change the communication rate of your network, make sure that all
devices change to the new communication rate. Mixed communication rates
produce communication errors.