Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 6

Configure Local I/O

2.

Select the Local Input/Test Output tab.

3.

Set the Error Latch Time.

The error latch time applies to all safety inputs and test outputs. It sets the
time to latch the error state when an error occurs in an input or output.
Even if the error is removed, the error state is always latched for the
configured error latch time. The error latch time is set from 0…65530 ms
in 10 ms increments. The default is 1000 ms.

4.

Select a safety input terminal and click Edit.

5.

Type an I/O Comment.

The I/O comment typed here is used as an I/O tag name in the Logic
Editor.