Monitor Status and Handle Faults

Chapter 12

2.

Click the EtherNet/IP Error History tab.

a. Click Save to save the error history data, which can also be saved in a

separate CSV file.

b. Click Clear to erase the error history saved in the controller.
c. Click Update to refresh the error history information.

Ethernet Error History Table

Error Code

Error

Detail Code

7-segment Display

1st Byte

(1)

2nd Byte

(1)

0602

CPU Bus Unit Memory

01: Read error

Variable

E9<->n4

02; Write error

020F

Communications Controller

00

01

F4<->n4

0211

Duplicate IP Address

02

Lower byte of IP address

F0<->n4

021A

Logic Error in Setting table

00

Variable

UF

03C4

Server Connection

04;BOOTP

01; Specific host does not exist

E3<0>n4

07: Transmission error

08: Reception error

0A: Obtaining IP address error