Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 32
Advertising

32
Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
Chapter 2
Installing and Wiring the SmartGuard 600 Controller
1.
Wire the connector according to the colors on the connector.
2.
Attach the connector to the
DeviceNet port.
3.
Tighten the screws to 0.25…0.3 N•m (2.21…2.65 lb•in).
For detailed DeviceNet connection information, refer to the DeviceNet Media
Design Installation Guide, publicatio
Industrial Automation Wiring and Grounding Guidelines, publication
Wire No.
Wire Color
Connects to
V+
Red
V+
CAN H
White
CAN H
Drain
—
Drain
CAN L
Blue
CAN L
V-
Black
V-
D
D
D
D
D
1
2
3
4
5
Advertising
This manual is related to the following products: