Chapter 2
Installing and Wiring the SmartGuard 600 Controller
1.
Wire the connector according to the colors on the connector.
2.
Attach the connector to the
DeviceNet port.
3.
Tighten the screws to 0.25…0.3 N•m (2.21…2.65 lb•in).
For detailed DeviceNet connection information, refer to the DeviceNet Media
Design Installation Guide, publicatio. Also refer to the
Industrial Automation Wiring and Grounding Guidelines, publication .
Wire No.
Wire Color
Connects to
V+
Red
V+
CAN H
White
CAN H
Drain
—
Drain
CAN L
Blue
CAN L
V-
Black
V-