Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 178

Advertising
background image

178

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 12

Monitor Status and Handle Faults

01:0115

Device type Error

The device data for the device in the RSNetWorx for DeviceNet configuration
file and the physical device in the system does not match. Use the Safety Device
Verification Wizard to check that the device in the system and the device in the
configuration file match. If they do match, re-configure the connections to the
safety master.

01:0116

Firmware Revision
Error

The device data for the device in the RSNetWorx for DeviceNet configuration
file and the physical device in the system does not match. Use the Safety Device
Verification Wizard to check that the device in the system and the device in the
configuration file match. If they do match, re-configure the connections
registered to the safety master.

01:0117

Connection Path Error

Two or more single-cast safety I/O connections or a multi-cast safety I/O
connection with a different RPI has been set for a safety slave I/O.
To share one safety slave I/O on a safety slave with more than one safety
master, make the RPI all the same and set the connection type to multi-cast.
SmartGuard controller safety slaves cannot have more than one single-cast
safety I/O connection for each safety slave I/O. Set multiple connection paths
for the controller’s safety slave I/O.
If previous solutions do not resolve the problem, delete and then re-configure
the connections to the safety master.

01:031E

Number of
Connections Error

The setting for the number of safety I/O connections exceeds the upper limit
supported by the safety slave. Adjust the safety connection setting for the
relevant safety master. In particular, check that no more than 15 safety masters
are set for each multi-cast connection, with a maximum total of 60.

01:031F

Connection ID
Resource Error

The maximum number of connection IDs for one safety master (12) has been
exceeded.
Click Advanced on the Safety Connection Properties dialog box. Check the
Request target device to allocate message IDs checkbox. Download the device
parameters to the safety master.

01:07FF

Non-existent Safety
Slave

The safety slave may not have been added to the network correctly. Check that
the corresponding safety slave is online. If the safety slave is not online, check
the following items:

·Is the node address for the safety slave correct?
·Do all nodes have the same communication rate?
·Is the cable length correct?
·Is the cable disconnected or slack?
·Is the terminating resistance only on both ends of the main line?
·Is there excessive noise?

01:080C

Safety Signature
Match

The safety signature for the safety slave monitored by the safety master does
not match the safety signature of the safety slave itself.
Reset the safety slave to default setting then download the device parameters
again.
If the above remedy does not work, delete then re-configure the connections
configured in the safety master.

01:080E

Safety Network
Number (SNN)
mismatch

The SNN for the safety slave monitored by the safety master does not match the
SNN of the safety slave itself.
Reset the safety slave to default settings, then download the correct device
parameters.
If the above remedy does not work, delete then re-configure the connections
configured in the safety master.

D0:0001

Idle Mode

The SmartGuard controller safety master is in the Idle mode, so safety I/O
connections have not been established.
Change the SmartGuard controller’s operating mode to Execute mode.

Code

Status

Corrective Action

Advertising