Muting Function Block Parameters

Set these parameters for the two-hand control function block.

Muting Function Block Optional Outputs

Optional outputs can also be used in programming. To use these optional
outputs, check the appropriate checkbox on the In/Out Setting tab of the
Function Block Properties dialog box in the Logic Editor of RSNetWorx for
DeviceNet software.

Overriding

Synchronization error

Sequence error

Discrepancy error (AOPD)

Discrepancy error (Override)

Table 28 - Muting Function Block Parameters

Parameter

Settings/Range

Default

Muting Mode

·Parallel muting with 2 sensors
This pattern is suitable for applications at a conveyor entrance. Use this pattern when two retro-reflective photoelectric
sensors are set up as muting sensors with intersecting detection zones.
·Sequential muting (forward direction)
This pattern is suitable for applications at a conveyor entrance. Use this pattern when four through-beam photoelectric
sensors are set up as muting sensors.
·Sequential muting (both directions)
This pattern is suitable for applications at a conveyor entrance or exit. Use this pattern when four through-beam
photoelectric sensors are set up as muting sensors.
·Position detection
This pattern is suitable for applications in which muting is controlled by a switch input. Use this pattern to temporarily
disable the light-interruption signal of the light curtain when an operator is placing an object in the machine opening,
and the machine is in a state where it will not harm the operator (hazards are in a different zone of the machine).

In all of these setting explanations, the muting sensors are on when detection is performed and off when detection is not
performed.

Parallel muting with 2
sensors

Synchronization Time

(1)

30 ms…3 seconds in 10 ms increments.
The timer SV must be longer than the controller’s cycle time.

3 seconds

Input Type of AOPD

·Dual Channel Equivalent (NC/NC)
·Dual Channel Complementary (NC/NO)

Dual Channel Equivalent

Discrepancy Time (AOPD)

10…500 ms in 10 ms increments

(2)

The timer SV must be longer than the controller’s cycle time.

30 ms

Input Type of Override
Signal

·Single Channel
·Dual Channel Equivalent (NO/NO)
·Dual Channel Complementary (NC/NO)
·Not Used

Not used

Discrepancy Time
(Override)

10…500 ms in 10 ms increments

(2)

The timer SV must be longer than the controller’s cycle time.

30 ms

Max Muting Time

500 ms…127.5 seconds in 500 ms increments
0…500 ms in 10 ms increments

60 seconds

Max Override Time

500 ms…127.5 seconds in 500 ms increments

60 seconds

(1) Between Muting Signal 11 and Muting Signal 12 or between Muting Signal 21 and Muting Signal 22.
(2) A discrepancy time check will not be performed is 0 is set.