You can reset the attributes shown on the Reset Safety Device dialog box by
checking their associated checkbox. Leaving an attribute checkbox blank
preserves that attribute’s setting during the safety reset operation.

1.

Open the Reset Safety Device dialog box by clicking on the device in the
RSNetWorx for DeviceNet software graphic view and selecting Reset
Safety Device from the Device menu.

2.

Check the attributes you want to reset.

3.

Click Reset.

If the device is safety-locked, you are prompted to first unlock the device.

4.

Type the password when prompted, if you have set a password for the
device.

Attribute

Reset Behavior

Configuration

The configuration of the device is erased as a result of any safety reset action.

Configuration Owner

Check this checkbox to reset the device’s configuration owner. The configuration
software is always the configuration owner for SmartGuard controllers.

Output Connection
Owner(s)

Check this checkbox to reset any existing output connection owners. The next device
that accesses an output connection point following the safety reset becomes the
output connection owner.

Password

Check this checkbox to reset the device password. You must know the current device
password to reset a password from the Reset Safety Device dialog box.

Address

Check this checkbox to reset the device’s software-configured node address to 63.
If the device’s node address has been set by using switches, the reset operation has no
effect on the node address.

Baud Rate

Check this checkbox to reset the device’s communication rate to 125 Kbps.
If the device’s communication rate has been set by using switches, the reset operation
has no effect on the communication rate.

Safety Network
Number

Check this checkbox to reset the device’s safety network number (SNN).

ATTENTION: Once unlocked, the device cannot be relied upon to
perform safety operations.

You must test and verify the device’s operation and run the Safety Device
Verification Wizard to safety-lock the device before operating the device in a
safety application.