Reset set fiip-flop error handling, Rs flip-flop instruction timing chart, Multi-connector instruction – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 212: Multi-connector instruction diagram

Advertising
background image

212

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Appendix C

Logic Functions Command Reference

Reset Set FIip-flop Error Handling

Use this table to diagnose and reset a discrepancy error condition in the RS Flip-
flop instruction.

RS Flip-flop Instruction Timing Chart

Multi-connector Instruction

The Multi-connector instruction converts input signals for up to eight inputs
into output signals for up to eight outputs. The input signals and output signals
are associated one-to-one for signals one to eight. The status of other input
signals has no effect.

The number of inputs and outputs can be increased to eight on the I/O Settings
tab of the Function Block Properties dialog box in RSNetWorx for DeviceNet
software. The default setting is one.

Multi-connector Instruction Diagram

Table 4 - Error Detection and Reset for RS Flip-flop Instruction

Error Condition

Status When an Error Occurs

To Reset the Error Condition

Output Enable

Fault

Present

Input and Reset are active

simultaneously

OFF

(Safety State)

ON

Make one of the signals inactive.

Input

Fault Present

Output Enable

Reset

Input 1

Input 2

Output 1

Input 1

Input 4

Input 3

Input 5
Input 6

Input 7
Input 8

Output 1

Output 2
Output 3
Output 4

Output 5

Output 6

Output 7

Output 8

Default Connections

Maximum I/O for Multi-connector Instruction

Advertising