Chapter 12

Monitor Status and Handle Faults

03D0

Ethernet Basic Setting

01: Ethernet Setting error

01: Checksum error

F2<->n4

11: Inconsistent setting

12; Specified baud rate is not
supported

02: TCP/IP Basic Setting error

01: Checksum error

11: Invalid IP address

12: Invalid subnet mask

13: Invalid default gateway address

14: Invalid primary name server

15: Invalid secondary name server

16: Invalid domain server

17: Invalid host name

03D5

Tag Data Link

00

Lower byte of IP address

L9<->n4

03D3

Link OFF

00

00

E1<->n4

(1) The first byte combined with the second byte appear as a single, 4-hex character in the Detailed Information column under the EtherNet/IP Error History tab. Refer to the dialog box in the Display the

EtherNet/IP Error History Table for the 1752-L24BBBE Controller section for examples.

Error Code

Error

Detail Code

7-segment Display

1st Byte

(1)

2nd Byte

(1)