B - status indicators, Introduction, Module status indicators – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 195: Appendix b, Status indicators, Introduction module status indicators, E appendix b, Appendix

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
195
Appendix
B
Status Indicators
Introduction
Module Status Indicators
Use these tables to interpret the color of the status indicators and take
recommended actions where applicable.
If your Module Status indicator is off, follow these steps.
1.
Cycle the power supply.
2.
Take corrective actions for noise.
3.
Contact Rockwell Automation.
If you Module Status indicator is flashing red, follow these steps.
1.
Configure the switches properly.
2.
Reset the configuration data.
Topic
Page
Identifying Errors Using Module Status Indicators and Alphanumeric Display
Identifying EtherNet/IP Errors Using Status Indicators and Alphanumeric Display
ATTENTION: Status indicators are not reliable indicators for safety functions.
They should be used only for general diagnostics during commissioning and
troubleshooting. Do not use status indicators as operational indicators.
If the Module Status (MS) indicator is
It means
Take this action
Off
No power.
Refer to the corrective action following this table.
Green, on
The controller is operating in Run mode and under normal
conditions.
No action required.
Green, flashing
The controller is idle.
Red, flashing
A recoverable fault exists.
Refer to the corrective action following this table.
Red, on
An unrecoverable fault exists.
Red/green flashing
Self-test in progress. Or, the controller’s configuration is
being downloaded or is incomplete or incorrect. For
example, the network ID (UNID) is not set.