B - status indicators, Introduction, Module status indicators – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 195: Appendix b, Status indicators, Introduction module status indicators, E appendix b, Appendix

Advertising
background image

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

195

Appendix

B

Status Indicators

Introduction

Module Status Indicators

Use these tables to interpret the color of the status indicators and take
recommended actions where applicable.

If your Module Status indicator is off, follow these steps.

1.

Cycle the power supply.

2.

Take corrective actions for noise.

3.

Contact Rockwell Automation.

If you Module Status indicator is flashing red, follow these steps.

1.

Configure the switches properly.

2.

Reset the configuration data.

Topic

Page

Module Status Indicators

195

Identifying Errors Using Module Status Indicators and Alphanumeric Display

199

Identifying EtherNet/IP Errors Using Status Indicators and Alphanumeric Display

202

ATTENTION: Status indicators are not reliable indicators for safety functions.
They should be used only for general diagnostics during commissioning and
troubleshooting. Do not use status indicators as operational indicators.

If the Module Status (MS) indicator is

It means

Take this action

Off

No power.

Refer to the corrective action following this table.

Green, on

The controller is operating in Run mode and under normal
conditions.

No action required.

Green, flashing

The controller is idle.

Red, flashing

A recoverable fault exists.

Refer to the corrective action following this table.

Red, on

An unrecoverable fault exists.

Red/green flashing

Self-test in progress. Or, the controller’s configuration is
being downloaded or is incomplete or incorrect. For
example, the network ID (UNID) is not set.

Advertising
This manual is related to the following products: