Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 267

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
267
Explicit Messages
Appendix E
Read Safety Input
Error Information
Cause
Read
Reads the cause for the
normal flag of the number
(1…16) specified by the
Instance ID being off (error).
0E hex
3D hex
01 to 10 hex
6E hex
—
1 byte
00 hex: no error
01 hex: invalid
configuration
02 hex: test signal error
03 hex: internal circuit
error
04 hex: discrepancy error
05 hex: error in other
channel of dual channels
Read AND of
Safety Input
Normal Flags
Read
Reads the cause for the
normal flag of the number
(1…16) specified by the
Instance ID being off (error).
0E hex
3E hex
01 hex
05 hex
—
1 byte
00 hex: error
01 hex: all normal
Read OR of
Monitor Status of
Input Total On
Times or Contact
Operation
Counters
Read
Reads the logical OR of the
monitor status of the total
on time or contact
operation counter for all
inputs 1…16.
0E hex
01 hex
72 hex
—
1 byte
00 hex: all in range
01 hex: input out of range
(over monitor value)
Table 42 - Setting and Monitoring Safety Input Terminals
Explicit
Message
Service
Function
Command
Response
Service
Code
Class ID
Instance ID
Attribute
ID
Data Size
Table 43 - Setting and Monitoring Safety Output Terminals
Explicit
Message
Service
Function
Command
Response
Service
Code
Class
ID
Instance ID
Attribute
ID
Data Size
Monitor Mode for
Terminal
Maintenance
Information
Read
Reads the monitor mode of
maintenance information for
the output (1…8) specified by
the Instance ID.
0E hex
3B hex
01…08 hex
65 hex
—
1 byte
00 hex: Total On Time mode
01 hex: Contact Operation
Counter mode
Write
Writes the monitor mode of
maintenance information for
the output (1…8) specified by
the Instance ID.
10 hex
3B hex
01…08 hex
65 hex
1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode
—
SV for Output
Total On Time or
Contact
Operation
Counter
Read
Reads the SV of the total on
time or contact operation
counter for the input (1…8)
specified by the Instance ID.
0E hex
3B hex
01…08 hex
68 hex
—
4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)
Write
Writes the SV of the total on
time or contact operation
counter for the input (1…8)
specified by the Instance ID.
10 hex
3B hex
01…08 hex
68 hex
4 bytes
0000 0000…
FFFF FFFF hex
(0…
4,294,967,295)
—
Read Output
Total On Time or
Contact
Operation
Counter
Read
Reads the total on time or
contact operation counter for
the input (1…8) specified by
the Instance ID.
0E hex
3B hex
01…08 hex
66 hex
—
4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)
Reset Output
Total On Time or
Contact
Operation
Counter
Reset
Resets to 0 the total on time or
contact operation counter for
the output (1…8) specified by
the Instance ID.
05 hex
3B hex
01…08 hex
66 hex
—
—