Explicit Messages

Appendix E

Read Safety Input
Error Information
Cause

Read

Reads the cause for the
normal flag of the number
(1…16) specified by the
Instance ID being off (error).

0E hex

3D hex

01 to 10 hex

6E hex

1 byte
00 hex: no error
01 hex: invalid
configuration
02 hex: test signal error
03 hex: internal circuit
error
04 hex: discrepancy error
05 hex: error in other
channel of dual channels

Read AND of
Safety Input
Normal Flags

Read

Reads the cause for the
normal flag of the number
(1…16) specified by the
Instance ID being off (error).

0E hex

3E hex

01 hex

05 hex

1 byte
00 hex: error
01 hex: all normal

Read OR of
Monitor Status of
Input Total On
Times or Contact
Operation
Counters

Read

Reads the logical OR of the
monitor status of the total
on time or contact
operation counter for all
inputs 1…16.

0E hex

01 hex

72 hex

1 byte
00 hex: all in range
01 hex: input out of range
(over monitor value)

Table 42 - Setting and Monitoring Safety Input Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class ID

Instance ID

Attribute
ID

Data Size

Table 43 - Setting and Monitoring Safety Output Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class
ID

Instance ID

Attribute
ID

Data Size

Monitor Mode for
Terminal
Maintenance
Information

Read

Reads the monitor mode of
maintenance information for
the output (1…8) specified by
the Instance ID.

0E hex

3B hex

01…08 hex

65 hex

1 byte
00 hex: Total On Time mode
01 hex: Contact Operation
Counter mode

Write

Writes the monitor mode of
maintenance information for
the output (1…8) specified by
the Instance ID.

10 hex

3B hex

01…08 hex

65 hex

1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode

SV for Output
Total On Time or
Contact
Operation
Counter

Read

Reads the SV of the total on
time or contact operation
counter for the input (1…8)
specified by the Instance ID.

0E hex

3B hex

01…08 hex

68 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)

Write

Writes the SV of the total on
time or contact operation
counter for the input (1…8)
specified by the Instance ID.

10 hex

3B hex

01…08 hex

68 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0…
4,294,967,295)

Read Output
Total On Time or
Contact
Operation
Counter

Read

Reads the total on time or
contact operation counter for
the input (1…8) specified by
the Instance ID.

0E hex

3B hex

01…08 hex

66 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)

Reset Output
Total On Time or
Contact
Operation
Counter

Reset

Resets to 0 the total on time or
contact operation counter for
the output (1…8) specified by
the Instance ID.

05 hex

3B hex

01…08 hex

66 hex

Advertising