Appendix C

Logic Functions Command Reference

AND Instruction

The output is the logical AND of up to eight input conditions. The number of
inputs can be set by using the In/Out Setting tab in the Function Block
Properties dialog box. The default setting is two inputs.

AND Instruction Diagram

AND Instruction Truth Tables

In the truth table, 0 is off and 1 is on. Lowercase x is don’t care.

Table 34 - Truth Table for One-input AND Evaluation

Input 1

Output 1

0

0

1

1

Table 35 - Truth Table for Two-input AND Evaluation

Input 1

Input 2

Output 1

0

x

0

x

0

0

1

1

1

Table 36 - Truth Table for Three-input AND Evaluation

Input 1

Input 2

Input3

Output 1

0

x

x

0

x

0

x

0

x

x

0

0

1

1

1

1

Output 1

Input 1

Input 2