Create Your Application Program
Chapter 10
Figure 40 - Function Block With Open Connections
To find all open connections in the Logic Editor, choose Edit>Search
OpenConnection.
The Open Connection dialog box shows all the function blocks with open
connections. Double-click an item on the list to display the function block. Open
connections are shown in red in the workspace.
Program on Multiple Pages
The SmartGuard 600 controller supports up to 32 pages of programming logic.
To create a new page, click the Add Page icon
.
Use jump addresses to connect logic between pages. A SmartGuard 600
controller program can contain up to 128 jump addresses.
Follow these steps to create a jump address.
1.
Right-click anywhere on the programming page and choose Make
JumpAddress.
2.
Type a name for the jump address.
TIP
If a jump address is used for the I/O point and the corresponding jump address
is not used, the I/O point will not be displayed in red and will appear to be
connected.
See Program on Multiple Pages on page 149 for information on jump
addresses.