Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 202

Advertising
background image

202

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Appendix B

Status Indicators

Identifying EtherNet/IP
Errors Using Status Indicators
and Alphanumeric Display

Use these tables to interpret the color and status combinations of the status and
alphanumeric display indicators and take corrective action where applicable.

For the 1752-L24BBBE controller, when the IP address display switch for 1
second or longer, the display shows the EtherNet/IP address that is set. The error
code ‘n4’ is displayed if an error occurs in EtherNet/IP configuration.

Table 33 - EtherNet/IP Controller Errors

Indicators

Error Log

Cause

Corrective Action

MS

NS

Alphanumeric Display

(1)

Code

Off

Red, on

UF

System Failure

An EtherNet/IP adaptor hardware fault
occurred.

Cycle the power supply. If a failure occurs
again, replace the controller.

Red, on

---

F0

An IP address duplication fault occurred.

Check the IP address of the other devices, and
set an address that does not duplicate any
other.

Off

---

E3

A BOOTP server connection fault occurred.

1. Make sure the cable is connected correctly.
2. Make sure the BOOTP server is operating

normally.

Off

---

F2

A Basic setting logic processing fault occurred. Check the configuration. If a failure occurs

again, replace the controller.

Off

Red,
flashing

E9

An EtherNet/IP memory fault occurred.

Cycle the power supply. If a failure occurs
again, replace the controller.

Off

Red,
flashing

F4

An EtherNet/IP communication controller
fault occurred.

Red,
flashing

---

L9

An EtherNet/IP standard target
communication error occurred.

1. Make sure the same communication

settings are used for each node

2. Make sure the cables are not disconnected

or bent.

3. Make sure power is supplied to the

originator.

Off

---

E1

A Link OFF error occurred.

1. Make sure the same communication

settings are used for each node

2. Make sure the cables are not disconnected

or bent.

3. Make sure power is supplied to the hub.

(1) Display alternates between error code and n4.

Advertising