Function Blocks Command Reference

Appendix D

Figure 68 - Application Setup

Sensor 11 is connected to Muting Signal 11. Sensor 12 is connected to Muting
Signal 12. Sensor 21 is connected to Muting Signal 21. Sensor 22 is connected to
Muting Signal 22.

Muting Sequence

The muting sequence for this example is described below.

1.

The light is not interrupted between sensors 11, 12, 21, and 22 and the
light curtain, so the Output Enable signal is on.

2.

For the entrance, as the workpiece moves to the right and sensors 11 and
12 go on in order (sensors 21 and 22 go on as the workpiece exits), muting
is enabled and the muting signal turns on.

3.

As the workpiece continues to advance, the Output Enable signal is kept
on even if the light curtain is obstructed.

4.

As the workpiece continues to advance, the workpiece is no longer
detected by sensor 21 at the entrance (sensor 12 during workpiece exit),
the muting status is cleared, and the muting signal turns off.

Sensor 11

Workpiece

L

V

Sensor 11

Sensor 12

Sensor 12

Sensor 21

Sensor 21

Sensor 22

Sensor 22

d2

D3

D2

Entrance

Sensor 11

Workpiece

L

V

Sensor 11

Sensor 12

Sensor 12

Sensor 21

Sensor 21

Sensor 22

Sensor 22

d2

D3

D2

Exit

Light Curtain

Light Curtain