Chapter 7

Configure Your Controller for DeviceNet Communication

4.

Click New.

5.

Click the I/O type: Poll, Bit-Strobe, COS, or Cyclic.

Output data cannot use a bit-strobe connection type because bitstrobe
data cannot be output from the standard master. Also, the maximum size
for bitstrobe data input to the standard master is 8 bytes. COS and cyclic
connections cannot be used at the same time.

6.

To add status information for Input types, check the Status checkboxes
(optional).

When the I/O type is Input, you can include the following status
information in the I/O assembly.

Tag Name

Data Size

Attribute Type

General Status

Byte

Non-safety

Local Input Status

Word

Non-safety

Local Output Status

Byte

Non-safety

Test Output/Muting Lamp Status

Byte

Non-safety