Wiring the smartguard 600 controller – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 2

Installing and Wiring the SmartGuard 600 Controller

standard Ethernet cable. When connecting the SmartGuard controller directly to
your personal computer or a NIC card, use a cross-over (null modem) cable.

Wiring the SmartGuard 600
Controller

Use cables of 30 m (98 ft) or less.

ATTENTION: The cable length must be less then 100 m (328 ft) between hub
and nodes.

WARNING: If you connect or disconnect the Ethernet cable with power applied
to this controller or any other device on this network, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

Pin No.

Pin Name

Pin placement

8

Not used

7

Not used

6

RD-

5

Not used

4

Not used

3

RD+

2

TD-

1

TD+

8

1

Attribute

Value

Wire type

Copper

Wiring category

(1)

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding

Guidelines, publication 1770-4.1.

2 - on power, signal, and communication ports

Wire size

For power supply and I/O, use 0.2…2.5 mm

2

(12…24 AWG) solid wire, or

0.34…1.5 mm

2

(16…22 AWG) stranded flexible wire. Before connecting,

prepare stranded wires by attaching ferrules with plastic insulation collars
(DIN 46228-4 standard compatible).

I/O Terminal Screw Torque

0.56…0.79 N•m (5…7 lb•in)

Terminal Designation

Description

V0

Power terminal for internal circuit (logic).

G0

Power terminal for internal circuit (logic).

V1

Power terminal for input circuits and test outputs.

G1

Power terminal for input circuits and test outputs.

V2

Power terminal for safety outputs.

G2

Power terminal for safety outputs.