Environmental specifications – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 191

Advertising
background image

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

191

Controller Specifications

Appendix A

Environmental Specifications

Ethernet communication

CIP connections

Not applicable

2

Auto negotiation

Not applicable

Supported

Data rate

Not applicable

10/100 Mbps

Duplex

Not applicable

Full/half

Allowable unit
communication bandwidth

Not applicable

3000 pps

(6)

Explicit message
communication

Not applicable

502 bytes

(7)

(1) V0/G0 for internal logic circuit; V1/G1 for external input devices and test outputs; V2/G2 for external output devices.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding

Guidelines, publication 1770-4.1.

(3) T0...T3 total current at the same time: 1.4 A.
(4) Height includes terminal connectors.
(5) Depth includes DeviceNet connector.
(6) PPS is packets per second. It indicates the number of send or receive packets that can be processed per second.
(7) The maximum message length for class 3 connection and UCMM connection.

Attribute

1752-L24BBB

1752-L24BBBE

Attribute

1752-L24BBB

1752-L24BBBE

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…70 °C (-40…158 °F)

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-10…55 °C (14…131 °F)

Relative humidity

IEC 60068-2-30
(Test Db, Unpackaged Nonoperating Damp Heat):
10…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
0.35 mm @ 10…57 Hz
5 g @ 57…150 Hz

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 15 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Enclosure type rating

Meets IP20

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

· 4 kV contact discharges

· 8 kV air discharges

IEC 61000-4-2:

· 6 kV contact discharges

· 8 kV air discharges

Advertising
This manual is related to the following products: