Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 5

Manage the Safety Network Number

Follow these steps if you need to set the SNN for a particular device.

1.

Click the target device in the hardware graphic view and choose Set Safety
Network Number from the Device menu.

2.

Choose Time-based and click Generate, or choose Manual and fill in a
decimal number from 1…9999.

3.

Click OK.

4.

Verify that the Network status indicator is rapidly alternating between red
and green on the correct device and click OK.

TIP

You can use the copy and paste buttons on the Set Safety Network
Number dialog box to copy and paste an SNN between devices and to
make a record of the SNN.

Advertising
This manual is related to the following products: