Manage the Safety Network Number
Follow these steps if you need to set the SNN for a particular device.
1.
Click the target device in the hardware graphic view and choose Set Safety
Network Number from the Device menu.
2.
Choose Time-based and click Generate, or choose Manual and fill in a
decimal number from 1…9999.
3.
Click OK.
4.
Verify that the Network status indicator is rapidly alternating between red
and green on the correct device and click OK.