Status Indicators

Appendix B

Identifying Errors Using
Module Status Indicators and
Alphanumeric Display

Use these tables to interpret the color and status combinations of the status and
alphanumeric display indicators and take corrective action where applicable.

Table 30 - Critical Errors

Indicators

Error Log

Cause

Corrective Action

MS

NS

Alphanumeric Display

Code

Off

Off

Off

None

Critical hardware fault.
Noise level higher than expected.

1. Cycle the power supply.
2. Check external wiring.
3. Take corrective actions for noise.
4. Contact Rockwell Automation.

Red, on

Off

Left: H
Right: ---

System Failure

Critical hardware fault.
Noise level higher than expected.
Output terminal shorted to 24V dc before
operation.

Red, on

Off

P6

System Failure

Output terminal shorted to 24V dc before
operation.

1. Cycle the power supply.
2. Check external wiring.

Table 31 - Abort Error

Indicators

Error Log

Cause

Corrective Action

MS

NS

Alphanumeric Display

(1)

Code

Red,
flashing

Green, on or
flashing

E8

Switch setting
mismatch

The node address and baud rate were
changed after the normal completion of
configuration download.

1. Set switches properly.
2. Reconfigure the device.

(1) Display alternates between error code and node address of the error.

Table 32 - Nonfatal Errors

Indicators

Error Log

Cause

Corrective Action

MS

Alphanumeric

Display

(1)

Code

I/O

Red, on

F0

---

Duplicate MAC ID

The same node address is set for more than
one node.

Check that node addresses have not been
duplicated and reconfigure the device if
necessary.

Red, on

F1

---

Bus Off

Communication is cut off because of frequent
data errors.

1. Make sure the communication rate is the

same for all nodes.

2. Check that cables are not loose,

disconnected, or too long.

3. Verify that terminating resistors have been

installed only at both ends of the main
line.

4. Take corrective action for noise.
5. Cycle the power supply.

Red,
flashing

L9

---

Standard I/O Connection
Timeout

Standard I/O connection timeout.

Red,
flashing

dA

---

Safety I/O Connection
Timeout

Safety I/O connection timeout.

Red,
flashing

d5

---

Nonexistent Slave Device

No slave detected.

Red,
flashing

d6

---

Safety I/O Connection
Establishment Failure

Safety I/O connection could not be
established.

Make sure the slave device is configured and
in a normal operational state.

Red,
flashing

d6

---

Invalid Slave Device

Invalid slave device due to verification error.

1. Verify the slave device’s configuration.
2. Connect a compatible slave device.

Off

E0

---

Network PS Voltage Low

Network power supply voltage is low.

1. Make sure the power supply voltage is set

within the specified range.

2. Check that cables or wires are not loose or

disconnected.