Appendix D

Function Blocks Command Reference

User Mode Switch Function Block Timing Chart

External Device Monitoring
(EDM)

Figure 60 - External Device Monitoring Function Block Diagram

The External Device Monitoring (EDM) function block evaluates the
Monitored Input signal and the status of an external device feedback signal
(EDM Feedback) and then turns on safety outputs to an external device.

If the Monitored Input signal turns on, the Output 1 and Output 2 signals turn
on. When this occurs, the status of the feedback signal must change within the
specified time. If the Monitored Input signal turns off, the Output 1 and Output
2 signals turn off. When this occurs, the status of the feedback signal must change
within the specified time.

If the status of the feedback signal does not change within the specified time, an
EDM error occurs, the Output 1 and Output 2 signals turn off, and the EDM
error signal turns on.

EDM Function Block Optional Outputs

Optional outputs can also be used in programming. To use these optional
outputs, check the appropriate checkbox on the Out point tab of the Function

Input 1

Idle to RUN

Input 2

Input 3

Output 1

Output 2

Output 3

2 seconds

2 seconds

2 seconds

Fault Present

!

!

!

EDM Feedback

Output 1

Monitored

Input

Default Connections

Maximum I/O for EDM Function

Output 2

EDM Error

EDM Feedback

Output 1

Monitored Input

Output 2

EDM Error

Fault Present