Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

223

Function Blocks Command Reference

Appendix D

ESTOP Function Block Error Handling

A discrepancy error is generated when one of the inputs is not in it’s correct state
for longer than the Discrepancy Time. For example, in Dual Channel Equivalent
mode, both inputs must be active (on) within the Discrepancy Time or an error
occurs.

Use this table to diagnose and reset a discrepancy error condition in the ESTOP
function block.

ESTOP Function Block Timing Chart

The chart shows the I/O timing when the function block is set up as Dual
Channel Equivalent.

Light Curtain (LC) Function
Block

Figure 51 - Light Curtain Function Block Diagram

Table 12 - Error Detection and Reset for ESTOP Function Block

Error

Condition

Status When an Error Occurs

To Reset the Error Condition

Output Enable

Fault

Present

Error Output

Discrepancy
Error

OFF
(Safety State)

ON

Discrepancy
Error Output:
ON

Remove the cause of the error and then
either:
1. Make the inputs active and inactive

again.

2. Change the controller’s operating

mode to Idle and back to Run.

Input 1 (NC)

Input 2 (NC)

Fault Present

Idle to Run

Output Enable

Discrepancy

Error

Discrepancy Time

!

!

Input 1 (NC)

Output Enable

Input 2 (NC)

Input 1 (NC)

Output Enable

Input 2 (NC)

Discrepancy Error

Fault Present

Default Connections

Maximum I/O for Light Curtain Function