Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 266

Advertising
background image

266

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Appendix E

Explicit Messages

Table 42 - Setting and Monitoring Safety Input Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class ID

Instance ID

Attribute
ID

Data Size

Monitor Mode for
Terminal
Maintenance
Information

Read

Reads the monitor mode of
maintenance information
for the input (1…16)
specified by the Instance ID.

0E hex

3D hex

01 to 10 hex

65 hex

1 byte
00 hex: Total On Time
mode
01 hex: Contact Operation
Counter mode

Write

Writes the monitor mode of
maintenance information
for the input (1…16)
specified by the Instance ID.

10 hex

3D hex

01 to 10 hex

65 hex

1 byte
00 hex: Total On Time
mode
01 hex: Contact
Operation Counter mode

SV for Input Total
On Time or
Contact Operation
Counter

Read

Reads the SV of the total on
time or contact operation
counter for the input
(1…16) specified by the
Instance ID.

0E hex

3D hex

01 to 10 hex

68 hex

4 bytes
0000 0000 …
FFFF FFFF hex
(0…4,294,967,295)

Write

Writes the SV of the total on
time or contact operation
counter for the input
(1…16) specified by the
Instance ID.

10 hex

3D hex

01 to 10 hex

68 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)

Read Input Total
On Time or
Contact Operation
Counter

Read

Reads the total on time or
contact operation counter
for the input (1…16)
specified by the Instance ID.

0E hex

3D hex

01 to 10 hex

66 hex

4 bytes
0000 0000 …
FFFF FFFF hex
(0…4,294,967,295)

Reset Input Total
On Time or
Contact Operation
Counter

Reset

Resets to 0 the total on time
or contact operation
counter for the input
(1…16) specified by the
Instance ID.

05 hex

3D hex

01 to 10 hex

66 hex

Read Monitor
Status of Input
Total On Time or
Contact Operation
Counter

Read

Reads the monitor status of
the total on time or contact
operation counter for the
input (1…16) specified by
the Instance ID.

0E hex

3D hex

01 to 10 hex

67 hex

1 byte
00 hex: in range
01 hex: out of range (over
monitor value)

Read Safety Input
Normal Flag

Read

Reads the normal flag
status of the number
(1…16) specified by the
Instance ID.

0E hex

3D hex

01 to 10 hex

04 hex

1 byte
00 hex: error
01 hex: normal

Advertising