Explicit Messages

Appendix E

Error Response Format

Like the normal response, the error response includes the Number of Receive
Bytes, the Originating Node Address, and Service Code. It also includes these
DeviceNet error codes.

Example Read Message from a GuardLogix Controller

This GuardLogix message instruction, programmed in RSLogix 5000 software
by using the command format parameters on page 261, reads the SmartGuard
data.

Table 37 - Local Outputs and Test Outputs (2 bytes)

Offset
(bytes)

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Safety Output
Terminal Number
7

Safety Output
Terminal Number
6

Safety Output
Terminal Number
5

Safety Output
Terminal Number
4

Safety Output
Terminal Number
3

Safety Output
Terminal Number
2

Safety Output
Terminal Number
1

Safety Output
Terminal Number
0

1

Reserved

Test Output
Terminal Number
3

Test Output
Terminal Number
2

Test Output
Terminal Number
1

Test Output
Terminal Number
0

Table 38 - DeviceNet Explicit Message Error Codes

Response Code

Error Name

Description

08FF

Service not supported

An error exists in the service code.

16FF

Object does not exist

The specified instance ID is not supported.

15FF

Too much data

The data is longer than the specified size.

13FF

Not enough data

The data is shorter than the specified size.

20FF

Invalid parameter

The specified operation command data is not supported.