Monitor Status and Handle Faults

Chapter 12

Local Output Status

When the bit is on, the status of the output is normal. When the bit is off, an
error has been detected

Test Output or Muting Lamp Status

When the bit is on, the status of the test output is normal. When the bit is off, an
error has been detected.

Controller Connection Status
(safety slave function)

Table 16 - Local Safety-Output Terminal Status

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal 7

Terminal 6

Terminal 5

Terminal 4

Terminal 3

Terminal 2

Terminal 1

Terminal 0

Table 17 - Test Output/Muting Lamp Status

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Terminal 3

disconnection

detected status

Reserved

Terminal 3

Terminal 2

Terminal 1

Terminal 0

Code

Status

Corrective Action

00:0001

Normal
communication

The safety I/O connection status is normal.

01:0001

Safety I/O Connection
Timeout

The safety I/O connection has timed out. Check the following:

·Do all nodes have the same baud rate?
·Is the cable length correct?
·Is the cable disconnected or slack?
·Is the terminating resistance only on both ends of the main line?
·Is there excessive noise?

01:0106

Output Connection
Owner Error

The safety slave established an output safety I/O connection with a safety
master that had a different node address last time.

01:0109

Data Size Error

The safety slave I/O size set to the SmartGuard controller safety slave and the
size set under the safety master safety connection setting does not match. The
safety slave I/O setting may have been changed so delete and then re-
configure the connections registered to the safety master.

01:0110

Unconfigured Device

The safety slave has not been configured. Download the device parameters to
the safety slave.

01:0111

RPI Error

The RPI set under the safety master safety connection is smaller than the safety
slave cycle time.

01:0113

Number of
Connections Error

The setting exceeds the maximum number of safety I/O connections supported
by the safety slave. Check the relevant safety master safety connection
settings.

01:0114

Vendor ID or Product
Code Error

The device data for the device in the RSNetWorx for DeviceNet configuration
file and the physical device in the system does not match. Use the Safety Device
Verification Wizard to check that the device in the system and the device in the
configuration file match. If they do match, re-configure the connections to the
safety master.