EN-14 Link Duplex

Option:

Function:

Forces the duplex for each port to Full or Half

duplex. If EN-12 Auto Negotiation is set to:

[ON], this parameter is read only.

[0]

Half Duplex

[1]

*

Full Duplex

EN-20 Control Instance

Range:

Function:

[None, 20, 21, 23,

100, 101, 103]

Read only. Displays the connection to

the master. In Ethernet/IP: If no CIP

connection is present, “None” is

displayed.

EN-21 Process Data Config Write

Range:

Function:

[[0 - 9] PCD read 0 - 9] Configuration of readable process

data.

EN-22 Process Data Config Read

Range:

Function:

[[0 - 9] PCD read 0 - 9] Configuration of readable process

data.

EN-28 Store Data Values

Option:

Function:

This parameter activates a function that stores

all parameter values in the non-volatile

memory (EEPROM) thus retaining parameter

values at power-down.

The parameter returns to “Off”.

[0]

*

Off

The store function is inactive.

[1]

Store All

set-ups

All parameter value will be stored in the non-

volatile memory, in all four setups.

EN-29 Store Always

Option:

Function:

Activates function that always stores received

parameter data in non-volatile memory (EEPROM).

[0]

*

Off

[1]

On

EN-30 Warning parameter

Range:

Function:

[0000–

FFFF hex]

Read only. Displays the Ethernet/IP specific 16-bit

Status-word.

Bit

Description

0

Owned

1

Not used

2

Configured

3

Not used

4

Not used

5

Not used

6

Not used

7

Not used

8

Minor recoverable fault

9

Minor unrecoverable fault

10

Major recoverable fault

11

Major unrecoverable fault

12

Not used

13

Not used

14

Not used

15

Not used

Table 3.27

EN-31 Net Reference

Option:

Function:

Read only. Displays the reference source in Instance

21/71.

[0]

*

Off

Reference from the network is not active.

[1]

On

Reference from the network is active.

EN-32 Net Control

Option:

Function:

Read only. Displays the control source in Instance

21/71.

[0]

*

Off

Control via the network is not active.

[1]

On

Control via the network is active

EN-33 CIP Revision

Option:

Function:

Read only. Displays the CIP-version of

the option software.

[0] Major version (00 - 99)

[1] Minor version (00-99)

EN-34 CIP Product Code

Range:

Function:

1100 (AF-650 GP) 1110

(AF-650 GP)

*

[0–9999] Read only. Displays the CIP

product code.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

103

3

3

Advertising