DR-16 Torque [Nm]

Range:

Function:

0 Nm

*

[-3000 -

3000

Nm]

View the torque value with sign, applied to

the motor shaft. Linearity is not exact between

160% motor current and torque in relation to

the rated torque. Some motors supply more

than 160% torque. Consequently, the min.

value and the max. value will depend on the

max. motor current as well as the motor used.

The value is filtered, and thus approx. 30 ms

may pass from when an input changes value

to when the data read-out values change.

DR-17 Speed [RPM]

Range:

Function:

0 RPM

*

[-30000 -

30000 RPM]

View the actual motor RPM. In open

loop or closed loop process control the

motor RPM is estimated. In speed

closed loop modes the motor RPM is

measured.

DR-18 Motor Thermal

Range:

Function:

0 %

*

[0 - 100

%]

View the calculated thermal load on the

motor. The cut-out limit is 100%. The basis for

calculation is the Electronic Thermal Overload

function selected in F-10 Electronic Overload.

DR-19 KTY sensor temperature

Range:

Function:

0 °C

*

[0 - 0 °C] Returning the actual temperature on KTY

sensor buil into the motor.

See parameter group F-1#.

DR-20 Motor Angle

Range:

Function:

0

*

[0 - 65535] View the current encoder/resolver angle offset

relative to the index position. The value range

of 0-65535 corresponds to 0-2*pi (radians).

DR-22 Torque [%]

Range:

Function:

0 %

*

[-200 - 200 %] Value shown is the torque in percent of

nominal torque, with sign, applied to the

motor shaft.

DR-25 Torque [Nm] High

Range:

Function:

0 Nm

*

[-200000000 -

200000000 Nm]

View the torque value with sign, applied

to the motor shaft. Some motors supply

more than 160% torque. Consequently,

the min. value and the max. value will

depend on the max. motor current as

well as the motor used. This specific

readout has been adapted to be able to

DR-25 Torque [Nm] High

Range:

Function:

show higher values than the standard

readout in DR-16 Torque [Nm].

3.18.3 DR-3# Drive Status

Parameters to view the drive status values.

DR-30 DC Link Voltage

Range:

Function:

0 V

*

[0 - 10000 V] View a measured value. The value is filtered

with an 30 ms time constant.

DR-32 Brake Energy /s

Range:

Function:

0 kW

*

[0 - 10000 kW] View the brake power transmitted to an

external brake resistor, stated as an

instantaneous value.

DR-33 Brake Energy /2 min

Range:

Function:

0 kW

*

[0 - 10000

kW]

View the brake power transmitted to an

external brake resistor. The mean power

is calculated on an average basis for the

most recent 120 s.

DR-34 Heatsink Temp.

Range:

Function:

0 °C

*

[0 - 255 °C] View the frequency converter heatsink

temperature. The cut-out limit is 90

±5 °C,

and the motor cuts back in at 60

±5 °C.

DR-35 Drive Thermal

Range:

Function:

0 %

*

[0 - 100 %]

View the percentage load on the inverter.

DR-36 Drive Nominal Current

Range:

Function:

10.00 A

*

[0.01 - 10000

A]

View the inverter nominal current,

which should match the nameplate

data on the connected motor. The data

are used for calculation of torque,

motor protection, etc.

DR-37 Drive Max. Current

Range:

Function:

16.00 A

*

[0.01 - 10000

A]

View the inverter maximum current,

which should match the nameplate

data on the connected motor. The data

are used for calculation of torque,

motor protection, etc.

Parameter Descriptions

AF-650 GP Programming Guide

114