GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 164

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter

Reference

15

Hardware mismatch

X

X

16

Short Circuit

X

X

17

Control word time-out

(X)

(X)

O-04 Control Word

Timeout Function

20

Temp. Input Error

21

Param Error

23

Internal Fans

X

24

External Fans

X

25

Brake resistor short-circuited

X

26

Brake resistor power limit

(X)

(X)

B-13 Braking Thermal

Overload

27

Brake chopper short-circuited

X

X

28

Brake check

(X)

(X)

B-15 Brake Check

29

Heatsink temp

X

X

X

30

Motor phase U missing

(X)

(X)

(X)

H-78 Missing Motor

Phase Function

31

Motor phase V missing

(X)

(X)

(X)

H-78 Missing Motor

Phase Function

32

Motor phase W missing

(X)

(X)

(X)

H-78 Missing Motor

Phase Function

33

Inrush Fault

X

X

34

Network communication fault

X

X

35

Option Fault

36

Mains failure

X

X

37

Phase imbalance

X

38

Internal Fault

X

X

39

Heatsink sensor

X

X

40

Overload of Digital Output Terminal 27

(X)

E-00 Digital I/O Mode,

E-51 Terminal 27 Mode

41

Overload of Digital Output Terminal 29

(X)

E-00 Digital I/O Mode,

E-52 Terminal 29 Mode

42

Ovrld X30/6-7

(X)

43

Ext. Supply (option)

45

Earth Fault 2

X

X

46

Pwr. card supply

X

X

47

24 V supply low

X

X

X

48

1.8 V supply low

X

X

49

Speed limit

X

H-36 Trip Speed Low

[RPM]

50

Auto Tune calibration failed

X

51

Auto Tune check U

nom

and I

nom

X

52

Auto Tune low I

nom

X

53

Auto Tune motor too big

X

54

Auto Tune motor too small

X

55

Auto Tune parameter out of range

X

56

Auto Tune interrupted by user

X

57

Auto Tune time-out

X

58

Auto Tune internal fault

X

X

59

Current limit

X

61

Feedback Error

(X)

(X)

H-20 Motor Feedback

Loss Function

62

Output Frequency at Maximum Limit

X

Troubleshooting

AF-650 GP Programming Guide

DET-618C

163

5

5

Advertising