WARNING/ALARM 34, Fieldbus communication fault
The network on the communication option card is not
working.

WARNING/ALARM 35, Option faultOut of frequency range
An option alarm is received. The alarm is option-specific.
The most likely cause is a power-up or a communication
fault.

WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and SP-10 Line failure is NOT
set to [0] No Function. Check the fuses to the frequency
converter and mains power supply to the unit.

ALARM 37, Phase imbalance
There is a current imbalance between the power units

ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
Table 5.4 is displayed.

Troubleshooting

Cycle power

Check that the option is properly installed

Check for loose or missing wiring

It may be necessary to contact your GE supplier or service
department. Note the code number for further trouble-
shooting directions.

No.

Text

0

Serial port cannot be restore. Contact your GE

supplier or GE Service Department.

256-258

Power EEPROM data is defective or too old.

Replace power card.

512-519

Internal fault. Contact your GE supplier or GE

Service Department.

783

Parameter value outside of min/max limits

1024-1284

Internal fault. Contact your GE supplier or the GE

Service Department.

1299

Option SW in slot A is too old

1300

Option SW in slot B is too old

1315

Option SW in slot A is not supported (not allowed)

1316

Option SW in slot B is not supported (not allowed)

1379-2819

Internal fault. Contact your GE supplier or GE

Service Department.

2561

Replace control card

2820

Keypad stack overflow

2821

Serial port overflow

2822

USB port overflow

3072-5122

Parameter value is outside its limits

5123

Option in slot A: Hardware incompatible with

control board hardware

5124

Option in slot B: Hardware incompatible with

control board hardware

5376-6231

Internal fault. Contact your GE supplier or GE

Service Department.

Table 5.4 Internal Fault Codes

ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.

The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.

WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-51 Terminal 27 Mode.

WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-52 Terminal 29 Mode.

WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check E-56 Term X30/6 Digi
Out (OPCGPIO)
.

For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check E-57 Term X30/7 Digi
Out (OPCGPIO)
.

ALARM 45, Earth fault 2
Earth (ground) fault on start-up.

Troubleshooting

Check for proper earthing (grounding) and loose
connections.

Check for proper wire size.

Check motor cables for short-circuits or leakage
currents.

ALARM 46, Power card supply
The supply on the power card is out of range.

There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
±18 V. When powered with three phase mains voltage, all
three supplies are monitored.

Troubleshooting

Check for a defective power card.

Check for a defective control card.

Check for a defective option card.

If a 24 V DC power supply is used, verify proper
supply power.

WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC backup power supply may be overloaded,
otherwise contact the GE supplier.

WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.