GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 49

Advertising
background image

[72]

Logic Rule 2

See parameter group LC-4#. If Logic Rule

2 is evaluated as TRUE, the output will

go high. Otherwise, it will be low.

[73]

Logic Rule 3

See parameter group LC-4#. If Logic Rule

3 is evaluated as TRUE, the output will

go high. Otherwise, it will be low.

[74]

Logic Rule 4

See parameter group LC-4#. If Logic Rule

4 is evaluated as TRUE, the output will

go high. Otherwise, it will be low.

[75]

Logic Rule 5

See parameter group LC-4#. If Logic Rule

5 is evaluated as TRUE, the output will

go high. Otherwise, it will be low.

[80]

Logic Controller

Digital Output

A

See LC-52 Logic Controller Action. The

output will go high whenever the Logic

Controller Action [38] Set dig. out. A high

is executed. The output will go low

whenever the Logic Controller Action

[32] Set dig. out. A low is executed.

[81]

Logic Controller

Digital Output B

See LC-52 Logic Controller Action. The

input will go high whenever the Logic

Controller Action [39] Set dig. out. A high

is executed. The input will go low

whenever the Logic Controller Action

[33] Set dig. out. A low is executed.

[82]

Logic Controller

Digital Output

C

See LC-52 Logic Controller Action. The

input will go high whenever the Logic

Controller Action [40] Set dig. out. A high

is executed. The input will go low

whenever the Logic Controller Action

[34] Set dig. out. A low is executed.

[83]

Logic Controller

Digital Output

D

See LC-52 Logic Controller Action. The

input will go high whenever the Logic

Controller Action [41] Set dig. out. A high

is executed. The input will go low

whenever the Logic Controller Action

[35] Set dig. out. A low is executed.

[84]

Logic Controller

Digital Output E

See LC-52 Logic Controller Action. The

input will go high whenever the Logic

Controller Action [42] Set dig. out. A high

is executed. The input will go low

whenever the Logic Controller Action

[36] Set dig. out. A low is executed.

[85]

Logic Controller

Digital Output F

See LC-52 Logic Controller Action. The

input will go high whenever the Logic

Controller Action [43] Set dig. out. A high

is executed. The input will go low

whenever the Logic Controller Action

[37] Set dig. out. A low is executed.

[120] Local reference

active

Output is high when F-02 Operation

Method = [2] Local or when

F-02 Operation Method = [0] Linked to

hand auto at the same time as the

keypad is in Hand mode.

[121] Remote

reference active

Output is high when F-02 Operation

Method = [1] Remote or [0] Linked to

hand/auto while the keypad is in [Auto]

mode.

[122] No alarm

Output is high when no alarm is present.

[123] Start command

active

Output is high when there is an active

Start command (i.e. via digital input bus

connection or [Hand] or [Auto]), and no

Stop or Start command is active.

[124] Running reverse Output is high when the frequency

converter is running counter clockwise

(the logical product of the status bits

‘running’ AND ‘reverse’).

[125] Drive in hand

mode

Output is high when the frequency

converter is in [Hand mode] (as indicated

by the LED light above [Hand]).

[126] Drive in auto

mode

Output is high when the frequency

converter is in [Hand] mode (as indicated

by the LED light above [Auto]).

E-20 Terminal 27 Digital Output

Choices are described under E-2#

E-21 Terminal 29 Digital Output

Choices are described under E-2#

E-24 Function Relay

Array [9]

(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay

6 [5], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])

Choices are described under E-2#

E-26 On Delay, Relay

Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5

[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])

Range:

Function:

0.01 s

*

[0.01 - 600 s] Enter the delay of the relay cut-in time.

The relay will only cut in if the condition

in E-24 Function Relay is uninterrupted

during the specified time. Select one of

available mechanical relays and OPCRLY

Relay Option Module in an array

function. See E-24 Function Relay.

Illustration 3.16 On Delay, Relay

Parameter Descriptions

AF-650 GP Programming Guide

48

DET-618C

3

3