5 c-## frequency control functions, 6 p-## motor data – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 146

Advertising
background image

Par. No.
#

Parameter description

Default value

4-set-up

Change

during

operation

Conver-

sion

index

Type

E-78

Pulse Output Max Freq #X30/6

5000 Hz

All set-ups

TRUE

0

Uint32

E-8#

E-80

Term 32/33 Pulses Per Revolution

1024 N/A

All set-ups

FALSE

0

Uint16

E-81

Term 32/33 Encoder Direction

[0] Clockwise

All set-ups

FALSE

-

Uint8

E-9#

E-90

Digital & Relay Bus Control

0 N/A

All set-ups

TRUE

0

Uint32

E-93

Pulse Out #27 Bus Control

0 %

All set-ups

TRUE

-2

N2

E-94

Pulse Out #27 Timeout Preset

0 %

1 set-up

TRUE

-2

Uint16

E-95

Pulse Out #29 Bus Control

0 %

All set-ups

TRUE

-2

N2

E-96

Pulse Out #29 Timeout Preset

0 %

1 set-up

TRUE

-2

Uint16

E-97

Pulse Out #X30/6 Bus Control

0 %

All set-ups

TRUE

-2

N2

E-98

Pulse Out #X30/6 Timeout Preset

0 %

1 set-up

TRUE

-2

Uint16

4.1.5 C-## Frequency Control Functions

Par. No.
#

Parameter description

Default value

4-set-up

Change

during

operation

Conver-

sion

index

Type

C-0#

C-01

Jump Frequency From [Hz]

ExpressionLimit

All set-ups

TRUE

-1

Uint16

C-02

Jump Speed From [RPM]

ExpressionLimit

All set-ups

TRUE

67

Uint16

C-03

Jump Speed To [RPM]

ExpressionLimit

All set-ups

TRUE

67

Uint16

C-04

Jump Frequency To [Hz]

ExpressionLimit

All set-ups

TRUE

-1

Uint16

C-05

Multi-step Frequency 1 - 8

0 %

All set-ups

TRUE

-2

Int16

C-2#

C-20

Jog Speed [Hz]

ExpressionLimit

All set-ups

TRUE

-1

Uint16

C-21

Jog Speed [RPM]

ExpressionLimit

All set-ups

TRUE

67

Uint16

C-22

Jog Accel/Decel Time

ExpressionLimit

All set-ups

TRUE

-2

Uint32

C-23

Quick Stop Decel Time

ExpressionLimit

2 set-ups

TRUE

-2

Uint32

C-24

Quick Stop Ramp Type

[0] Linear

All set-ups

TRUE

-

Uint8

C-25

Quick Stop S-ramp Ratio at Decel. Start

50 %

All set-ups

TRUE

0

Uint8

C-26

Quick Stop S-ramp Ratio at Decel. End

50 %

All set-ups

TRUE

0

Uint8

C-3#

C-30

Frequency Command 2

ExpressionLimit

All set-ups

TRUE

-

Uint8

C-34

Frequency Command 3

ExpressionLimit

All set-ups

TRUE

-

Uint8

4.1.6 P-## Motor Data

Par. No.
#

Parameter description

Default value

4-set-up

Change

during

operation

Conver-

sion

index

Type

P-0#

P-01

Motor Poles

ExpressionLimit

All set-ups

FALSE

0

Uint8

P-02

Motor Power [HP]

ExpressionLimit

All set-ups

FALSE

-2

Uint32

P-03

Motor Current

ExpressionLimit

All set-ups

FALSE

-2

Uint32

P-04

Auto Tune

[0] Off

All set-ups

FALSE

-

Uint8

P-05

Motor Cont. Rated Torque

ExpressionLimit

All set-ups

FALSE

-1

Uint32

P-06

Base Speed

ExpressionLimit

All set-ups

FALSE

67

Uint16

P-07

Motor Power [kW]

ExpressionLimit

All set-ups

FALSE

1

Uint32

P-09

Slip Compensation

100 %

All set-ups

TRUE

0

Int16

P-1#

Parameter Lists

AF-650 GP Programming Guide

DET-618C

145

4