H-21 motor, Feedback speed error, H-22 motor feedback – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 63: Loss timeout, H-21 motor feedback speed error, 3 h-4# advanced settings

Advertising
background image

of H-22 Motor Feedback Loss Timeout. Warning/Alarm 61
Feedback Error is related to the Motor Feedback Loss
Function.

H-21 Motor Feedback Speed Error

Range:

Function:

300 RPM

*

[1 - 600 RPM] Select the max allowed error in speed

(output speed vs. feedback).

Illustration 3.23 Motor Feedback Speed Error

H-22 Motor Feedback Loss Timeout

Range:

Function:

0.05 s

*

[0 - 60 s] Set the timeout value allowing the speed

error set in H-21 Motor Feedback Speed Error

to be exceeded before enabling the function

selected in H-20 Motor Feedback Loss

Function.

H-24 Tracking Error Function

Option:

Function:

This function is used to monitor that the

application follows the expected speed profile.

In Closed loop the speed reference to the PID

is compared to the encoder feedback (filtered)

In open loop the speed reference to the PID is

compensated for slip and compared to the

frequency that is sent to the motor

(DR-13 Frequency).

The reaction will be activated if the measured

difference is more than specified in

H-25 Tracking Error for the time specified in

H-26 Tracking Error Timeout.

A tracking error in closed loop does not imply

that there is a problem with the feedback

signal! A tracking error can be the result of

torque limit at too big loads.

[0]

*

Disable

H-24 Tracking Error Function

Option:

Function:

[1]

Warning

[2]

Trip

[3]

Trip after

stop

Warning/Alarm 78 Tracking Error is related to the Tracking
Error Function.

H-25 Tracking Error

Range:

Function:

10 RPM

*

[1 - 600

RPM]

Enter the maximum permissible speed

error between the motor speed and the

output of the ramp when not ramping. In

open loop the motor speed is estimated

and in closed loop it is the feedback from

encoder/resolver.

H-26 Tracking Error Timeout

Range:

Function:

1 s

*

[0 - 60 s] Enter the time-out period during which an error

greater than the value set in H-25 Tracking Error

is permissible.

H-27 Tracking Error Ramping

Range:

Function:

100 RPM

*

[1 - 600

RPM]

Enter the maximum permissible speed

error between the motor speed and the

output of the ramp when ramping. In

open loop the motor speed is estimated

and in closed loop it is the feedback

from encoder/resolver.

H-28 Tracking Error Ramping Timeout

Range:

Function:

1 s

*

[0 - 60 s] Enter the time-out period during which an error

greater than the value set in H-27 Tracking Error

Ramping while Ramping is permissible.

H-29 Tracking Error After Ramping Timeout

Range:

Function:

5 s

*

[0 - 60 s] Enter the time-out period after ramping where

H-27 Tracking Error Ramping and H-28 Tracking

Error Ramping Timeout are still active.

3.7.3 H-4# Advanced Settings

Parameters to configure advanced controls for Open/
Closed Loop, control principles: V/Hz, Adv. Vector,
Sensorless Vector, and Closed Loop Vector, Constant or
Variable Torque, and Overload Mode.

Parameter Descriptions

AF-650 GP Programming Guide

62

DET-618C

3

3

Advertising