K-10 Active Set-up

Option:

Function:

[0]

Factory setup Cannot be changed. It contains the GE data

set, and can be used as a data source when

returning the other set-ups to a known

state.

[1]

*

Set-up 1

[1] Set-up 1 to [4] Set-up 4 are the four

separate parameter set-ups within which all

parameters can be programmed.

[2]

Set-up 2

[3]

Set-up 3

[4]

Set-up 4

[9]

Multi Set-up

Remote selection of set-ups using digital

inputs and the serial communication port.

This set-up uses the settings from K-12 This

Set-up Linked to. Stop the frequency

converter before making changes to open-

and closed loop functions

Use K-51 Set-up Copy to copy a set-up to one or all other
set-ups. Stop the frequency converter before switching
between set-ups where parameters marked ‘not
changeable during operation’ have different values. To
avoid conflicting settings of the same parameter within
two different set-ups, link the set-ups together using
K-12 This Set-up Linked to. Parameters which are ‘not
changeable during operation’ are marked FALSE in the
parameter lists in 4 Parameter Lists.

K-11 Edit Set-up

Option:

Function:

Select the set-up to be edited (i.e.

programmed) during operation; either the

active set-up or one of the inactive set-ups.

[0]

Factory setup Cannot be edited but it is useful as a data

source to return the other set-ups to a

known state.

[1]

*

Set-up 1

[1] Set-up 1 to [4] Set-up 4 can be edited

freely during operation, independently of

the active set-up.

[2]

Set-up 2

[3]

Set-up 3

[4]

Set-up 4

[9]

Active Set-up Can also be edited during operation. Edit

the chosen set-up from a range of sources:

Keypad, Drive RS-485, Drive USB or up to

five Network sites.

Illustration 3.1 Edit Set-up

K-12 This Set-up Linked to

Option:

Function:

To enable conflict-free changes from one set-up

to another during operation, link set-ups

containing parameters which are not

changeable during operation. The link will

ensure synchronising of the ‘not changeable

during operation’ parameter values when

moving from one set-up to another during

operation. ‘Not changeable during operation’

parameters can be identified by the label FALSE

in the parameter lists in 4 Parameter Lists.

K-12 This Set-up Linked to is used by Multi set-

up in K-10 Active Set-up. Multi set-up is used to

move from one set-up to another during

operation (i.e. while the motor is running).

Example:

Use Multi set-up to shift from Set-up 1 to Set-

up 2 whilst the motor is running. Program in

Set-up 1 first, then ensure that Set-up 1 and

Set-up 2 are synchronised (or ‘linked’). Synchro-

nisation can be performed in two ways:

1. Change the edit set-up to [2] Set-up 2 in

K-11 Edit Set-up and set K-12 This Set-up Linked

to to [1] Set-up 1. This will start the linking

(synchronising) process.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

25