GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 99

Advertising
background image

PB-16 PCD Read Configuration

[10] Array

Option:

Function:

[1248] Speed Ref. After Ramp [RPM]

[1250] External Reference

[1251] Pulse Reference

[1252] Feedback[Unit]

[1253] Digi Pot Reference

[1257] Feedback [RPM]

[1260] Digital Input

[1261] Terminal 53 Switch Setting

[1262] Analog Input 53

[1263] Terminal 54 Switch Setting

[1264] Analog Input 54

[1265] Analog Output 42 [mA]

[1266] Digital Output [bin]

[1267] Freq. Input #29 [Hz]

[1268] Freq. Input #33 [Hz]

[1269] Pulse Output #27 [Hz]

[1270] Pulse Output #29 [Hz]

[1271] Relay Output [bin]

[1272] Counter A

[1273] Counter B

[1274] Prec. Stop Counter

[1275] Analog In X30/11

[1276] Analog In X30/12

[1277] Analog Out X30/8 [mA]

[1284] Comm. Option STW

[1285] Drive Port CTW 1

[1287] Bus Readout Alarm/Warning

[1290] Alarm Word

[1291] Alarm Word 2

[1292] Warning Word

[1293] Warning Word 2

[1294] Ext. Status Word

[1500] Operating hours

[1501] Running Hours

[1502] kWh Counter

PB-18 Node Address

Range:

Function:

126

*

[0 -

126]

Enter the station address in this parameter or

alternatively in the hardware switch. In order to

adjust the station address in PB-18 Node Address,

the hardware switch must be set to 126 or 127

(that is, all switches set to ‘on’). Otherwise this

parameter displays the actual setting of the

switch.

PB-22 Telegram Selection

Displays the Profibus message configuration.

Option:

Function:

[1]

Standard telegram 1

[100]

*

None

PB-22 Telegram Selection

Displays the Profibus message configuration.

Option:

Function:

[101]

PPO 1

[102]

PPO 2

[103]

PPO 3

[104]

PPO 4

[105]

PPO 5

[106]

PPO 6

[107]

PPO 7

[108]

PPO 8

Read only.

[200]

Custom telegram 1

[202]

Custom telegram 3

PB-23 Parameters for Signals

Array [1000]

Read only

Option: Function:

This parameter contains a list of signals available for

selection in PB-15 PCD Write Configuration and

PB-16 PCD Read Configuration.

PB-27 Parameter Edit

Option:

Function:

Parameters can be edited via Profibus, the

standard RS-485 interface, or the keypad.

[0]

Disabled Disables editing via Profibus.

[1]

*

Enabled

Enables editing via Profibus.

PB-28 Process Control

Option:

Function:

Process control (setting of Control Word, speed

reference, and process data) is possible via

either Profibus or standard Network but not

both simultaneously. Local control is always

possible via the keypad. Control via process

control is possible via either terminals or

Network depending on the settings in

O-50 Coasting Select to O-56 Preset Reference

Select.

[0]

Disable

Disables process control via Profibus, and

enables process control via standard Network or

Profibus Master class 2.

[1]

*

Enable

cyclic

master

Enables process control via Profibus Master Class

1, and disables process control via standard

Network or Profibus Master class 2.

PB-44 Fault Message Counter

Range:

Function:

0

*

[0 - 65535] This parameter displays the number of error

events stored in PB-45 Fault Code and

PB-47 Fault Number. The maximum buffer

Parameter Descriptions

AF-650 GP Programming Guide

98

DET-618C

3

3