3.5 C-##

Frequency

Control Functions

Parameter group related to the Jump Frequencies, Multi-
step Frequencies, Job set-up, and Frequency Settings 2
and 3.

3.5.1 C-0# Frequency Control Functions

Parameters to configure Jump Frequencies 1, 2, 3, and 4,
and Multi-step Frequencies 1 through 8.

C-01 Jump Frequency From [Hz]

Array [4]

Range:

Function:

0 Hz

*

[0 - par. F-15

Hz]

Some systems call for avoiding certain

output speeds due to resonance

problems in the system. Enter the lower

limits of the speeds to be avoided.

C-02 Jump Speed From [RPM]

Array [4]

Range:

Function:

0 RPM

*

[0 - par. F-17

RPM]

Some systems call for avoiding certain

output speeds due to resonance

problems in the system. Enter the

lower limits of the speeds to be

avoided.

C-03 Jump Speed To [RPM]

Array [4]

Range:

Function:

0 RPM

*

[0 - par. F-17

RPM]

Some systems call for avoiding certain

output speeds due to resonance

problems in the system. Enter the

upper limits of the speeds to be

avoided.

C-04 Jump Frequency To [Hz]

Array [4]

Range:

Function:

0 Hz

*

[0 - par. F-15

Hz]

Some systems call for avoiding certain

output speeds due to resonance

problems in the system. Enter the upper

limits of the speeds to be avoided.

C-05 Multi-step Frequency 1 - 8

Array [8]

Range: 0-7

Range:

Function:

0 %

*

[-100 -

100 %]

Enter up to eight different preset references

(0-7) in this parameter, using array

programming. The preset reference is stated as

a percentage of the value Ref

MAX

(F-53 Maximum Reference) If a Ref

MIN

different

C-05 Multi-step Frequency 1 - 8

Array [8]

Range: 0-7

Range:

Function:

from 0 (F-52 Minimum Reference) is

programmed, the preset reference is calculated

as a percentage of the full reference range, i.e.

on the basis of the difference between Ref

MAX

and Ref

MIN

. Afterwards, the value is added to

Ref

MIN

. When using preset references, select

Preset ref. bit 0/1/2 [16], [17] or [18] for the

corresponding digital inputs in parameter

group E-##.

Illustration 3.18 Preset Reference

Preset ref. bit

2

1

0

Preset ref. 0

0

0

0

Preset ref. 1

0

0

1

Preset ref. 2

0

1

0

Preset ref. 3

0

1

1

Preset ref. 4

1

0

0

Preset ref. 5

1

0

1

Preset ref. 6

1

1

0

Preset ref. 7

1

1

1

Table 3.12 Preset Ref. Bit

3.5.2 C-2# Jog Set-Up

Parameters to configure Jog Speed, Jog Accel/Decel Time
and Quick Stop Decel Time.

C-20 Jog Speed [Hz]

Range:

Function:

0 Hz

*

[0 - par. F-15

Hz]

The jog speed is a fixed output speed at

which the frequency converter is running

when the jog function is activated.

See also C-22 Jog Accel/Decel Time.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

53