DN-13 Warning Parameter

Range:

Function:

0

*

[0 -

65535]

View a DeviceNet-specific Warning word. One bit

is assigned to every warning. Please refer to the

DeviceNet Operating Instructions for further

information.

Bit

Meaning

0

not active

1

Explicit connection timeout

2

I/O connection

3

Retry limit reached

4

Actual is not updated

5

CAN bus off

6

I/O send error

7

Initialization error

8

No bus supply

9

Bus off

10

Error passive

11

Error warning

12

Duplicate MAC ID Error

13

RX queue overrun

14

TX queue overrun

15

CAN overrun

Table 3.25

DN-14 Net Reference

Read only from keypad

Option:

Function:

Select the reference source in Instance 21/71 and

20/70.

[0]

*

Off

Enables reference via analog/digital inputs.

[1]

On

Enables reference via the network.

DN-15 Net Control

Read only from keypad

Option:

Function:

Select the control source in Instance 21/71 and 20/70.

[0]

*

Off Enables control via analog/digital inputs.

[1]

On Enable control via the network.

3.11.3 DN-2# COS Filters

Parameters to configure the filtering of Change of State
data.

DN-20 COS Filter 1

Range:

Function:

0

*

[0 - 65535] Enter the value for COS Filter 1 to set up the

filter mask for the Status Word. When operating

in COS (Change-Of-State), this function filters

out bits in the Status Word that should not be

sent if they change.

DN-21 COS Filter 2

Range:

Function:

0

*

[0 - 65535] Enter the value for COS Filter 2, to set up the

filter mask for the Main Actual Value. When

operating in COS (Change-Of-State), this

function filters out bits in the Main Actual Value

that should not be sent if they change.

DN-22 COS Filter 3

Range:

Function:

0

*

[0 - 65535] Enter the value for COS Filter 3, to set up the

filter mask for PCD 3. When operating in COS

(Change-Of-State), this function filters out bits in

PCD 3 that should not be sent if they change.

DN-23 COS Filter 4

Range:

Function:

0

*

[0 - 65535] Enter the value for COS Filter 4 to set up the

filter mask for PCD 4. When operating in COS

(Change-Of-State), this function filters out bits in

PCD 4 that should not be sent if they change.

3.11.4 DN-3# Parameter Access

Parameters to configure the acces to indexed parameters
and defining programming set-up.

DN-30 Array Index

Range:

Function:

0

*

[0 - 255] View array parameters. This parameter is valid only

when a DeviceNet fieldbus is installed.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

95