O-43 PCD Read Configuration

Range:

Function:

[1250]

External Reference

[1251]

Pulse Reference

[1252]

Feedback[Unit]

[1253]

Digi Pot Reference

[1257]

Feedback [RPM]

[1260]

Digital Input

[1261]

Terminal 53 Switch Setting

[1262]

Analog Input 53

[1263]

Terminal 54 Switch Setting

[1264]

Analog Input 54

[1265]

Analog Output 42 [mA]

[1266]

Digital Output [bin]

[1267]

Freq. Input #29 [Hz]

[1268]

Freq. Input #33 [Hz]

[1269]

Pulse Output #27 [Hz]

[1270]

Pulse Output #29 [Hz]

[1271]

Relay Output [bin]

[1272]

Counter A

[1273]

Counter B

[1274]

Prec. Stop Counter

[1275]

Analog In X30/11

[1276]

Analog In X30/12

[1277]

Analog Out X30/8 [mA]

[1284]

Comm. Option STW

[1285]

Drive Port CTW 1

[1287]

Bus Readout Alarm/Warning

[1290]

Alarm Word

[1291]

Alarm Word 2

[1292]

Warning Word

[1293]

Warning Word 2

[1294]

Ext. Status Word

[1500]

Operating hours

[1501]

Running Hours

[1502]

kWh Counter

3.10.5 O-5# Digital/Bus

Parameters to configure the control word Digital/Bus
merging.

O-50 Coasting Select

Option:

Function:

Select control of the coasting function via the

terminals (digital input) and/or via the network.

[0]

Digital

input

Activates Coast command via a digital input.

[1]

Bus

Activates Coast command via the serial

communication port or network option

module.

[2]

Logic AND

Activates Coast command via the network/

serial communication port, AND additionally

via one of the digital inputs.

O-50 Coasting Select

Option:

Function:

[3]

*

Logic OR

Activates Coast command via the network/

serial communication port OR via one of the

digital inputs.

O-51 Quick Stop Select

Select control of the Quick Stop function via the terminals

(digital input) and/or via the network.

Option:

Function:

[0]

Digital input

[1]

Bus

[2]

Logic AND

[3]

*

Logic OR

O-52 DC Brake Select

Option:

Function:

Select control of the DC brake via the terminals

(digital input) and/or via the fieldbus.

NOTE

Only selection [0] Digital input is available
when P-20 Motor Construction is set to [1]
PM non-salient SPM
.

[0]

*

Digital

input

ActivatesDC Brake command via a digital input.

[1]

Bus

ActivatesDC Brake command via the serial

communication port or network option module.

[2]

Logic AND ActivatesDC Brake command via the network/

serial communication port, AND additionally via

one of the digital inputs.

[3]

Logic OR

ActivatesDC Brake command via the network/

serial communication port OR via one of the

digital inputs.

O-53 Start Select

Option:

Function:

Select control of the frequency converter start

function via the terminals (digital input) and/or

via the network.

[0]

Digital

input

Activates Start command via a digital input.

[1]

Bus

Activates Start command via the serial

communication port or network option

module.

[2]

Logic AND

Activates Start command via the network/serial

communication port, AND additionally via one

of the digital inputs.

[3]

*

Logic OR

Activates Start command via the network/serial

communication port OR via one of the digital

inputs.