H-53 Model Shift Frequency

Range:

Function:

Illustration 3.28 H-40 = [1] Speed closed loop or

[2] Torque and H-41 = [3] Flux w/motor

feedback

Variable Current - Flux model - Sensorless

This model is used when H-40 is set to [0]Speed

open loop and H-41 is set to [2] Flux sensorless.

In speed open loop in flux mode, the speed is

determined from the current measurement.

Below f

norm

x 0.1, the drive runs on a Variable

Current model. Above f

norm

x 0.125 the frequency

converter runs on a Flux model.

Illustration 3.29 H-40 = [0] Speed open loop,

H-41 = [2] Flux sensorless

H-55 U/f Characteristic - U

Range:

Function:

0 V

*

[0 - 1000

V]

Enter the voltage at each frequency point to

manually form a U/f characteristic matching

the motor.

The frequency points are defined in H-56 U/f

Characteristic - F.

This parameter is an array parameter [0-5] and

is only accessible when H-41 Motor Control

Principle is set to [0] U/f.

H-56 U/f Characteristic - F

Range:

Function:

0 Hz

*

[0 - 1000.0

Hz]

Enter the frequency points to manually

form a U/f-characteristic matching the

motor.

The voltage at each point is defined in

H-55 U/f Characteristic - U.

H-56 U/f Characteristic - F

Range:

Function:

This parameter is an array parameter [0-5]

and is only accessible when H-41 Motor

Control Principle is set to [0] U/f.

Illustration 3.30 U/f Characteristic

H-58 Flystart Test Pulses Current

Range:

Function:

0 %

*

[0 -

0 %]

Sets the current level for the flystart test pulses

that are used to detect the motor direction. 100%

means I

m,n

. Adjust the value to be big enough to

avoid noise influence but low enough to avoid

affecting the accuracy (current must be able to

drop to zero before the next pulse). Reduce the

value to reduce the generated torque.

Default is 30% for asynchronous motors, but may

vary for PM motors. For PM motors adjusting the

value will tune for back EMF and d-axis inductance

of the motor.

This parameter is only available in Advanced Vector

Control.

H-59 Flystart Test Pulses Frequency

Range:

Function:

0 %

*

[0 - 0

%]

Sets the frequency of the flystart test pulses that

are used to detect the motor direction. 100%

means means 2 x fslip. Increase this value to

reduce the generated torque. For PM motors this

value is the percentage nm,n of the free running

PM motor. Above this value flystart is always

performed. Below this value, the start mode is

selected in F-20 PM Start Mode

This parameter is only available in Advanced

Vector Control.

3.7.5 H-6# Load Depen. Settings

Parameters to configure the load-dependent motor
settings.

Parameter Descriptions