2 id-1# data trending settings – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 110

Advertising
background image

NOTE

The reset is carried out by pressing [OK].

ID-07 Reset Running Hours Counter

Option:

Function:

[0]

*

Do not reset

[1]

Reset counter Select [1] Reset and press [OK] to reset the

Running Hours counter to zero (see

ID-01 Running Hours). This parameter cannot

be selected via the serial port, RS-485.

Select [0] Do not reset if no reset of the

Running Hours counter is desired.

ID-08 Number of Starts

Range:

Function:

0

*

[0 - 2147483647] This is a read out parameter only. The

counter shows the numbers of starts and

stops caused by a normal Start/Stop

command and/or when entering/leaving

sleep mode.

NOTE

This parameter will be reset when resetting ID-07 Reset
Running Hours Counter
.

3.17.2 ID-1# Data Trending Settings

Data Log Settings enables continous logging of up to 4
data sources (ID-10 Trending Source) at individual rates
(ID-11 Trending Interval). A trigger event (ID-12 Trigger
Event
) a
nd window (ID-14 Samples Before Trigger) are used
to start and stop the logging conditionally.

ID-10 Trending Source

Array [4]

Option:

Function:

Select which variables are

to be logged.

[0]

*

None

[515]

Readout: actual setup

[1200] Control Word

[1201] Reference [Unit]

[1202] Reference %

[1203] Status Word

[1210] Power [kW]

[1211] Power [hp]

[1212] Motor Voltage

[1213] Frequency

[1214] Motor current

[1216] Torque [Nm]

[1217] Speed [RPM]

[1218] Motor Thermal

[1221] Torque [%] High Res.

[1222] Torque [%]

ID-10 Trending Source

Array [4]

Option:

Function:

[1225] Torque [Nm] High

[1230] DC Link Voltage

[1232] Brake Energy /s

[1233] Brake Energy /2 min

[1234] Heatsink Temp.

[1235] Drive Thermal

[1248] Speed Ref. After Ramp [RPM]

[1250] External Reference

[1251] Pulse Reference

[1252] Feedback[Unit]

[1257] Feedback [RPM]

[1260] Digital Input

[1262] Analog Input 53

[1264] Analog Input 54

[1265] Analog Output 42 [mA]

[1266] Digital Output [bin]

[1275] Analog In X30/11

[1276] Analog In X30/12

[1277] Analog Out X30/8 [mA]

[1290] Alarm Word

[1292] Warning Word

[1294] Ext. Status Word

ID-11 Trending Interval

Array [4]

Range:

Function:

0.000

*

[0.000 - 0.000] Enter the interval in milliseconds

between each sampling of the variables

to be logged.

ID-12 Trigger Event

Select the trigger event. When the trigger event occurs, a

window is applied to freeze the log. The log will then retain a

specified percentage of samples before the occurrence of the

trigger event (ID-14 Samples Before Trigger).

Choices are described under E-## Digital Output.

Option:

Function:

[0]

*

False

[1]

True

[2]

Running

[3]

In range

[4]

On reference

[5]

Torque limit

[6]

Current Limit

[7]

Out of current range

[8]

Below I low

[9]

Above I high

[10]

Out of speed range

[11]

Below speed low

[12]

Above speed high

[13]

Out of feedb. range

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

109

3

3