H-40 Configuration Mode

Option:

Function:

Select the application control principle to be

used when a Remote Reference (i.e. via

analog input or Network) is active. A Remote

Reference can only be active when

F-02 Operation Method is set to [0] Linked to

Hand/Auto or [1] Remote.

[0]

*

Speed open

loop

Enables speed control (without feedback

signal from motor) with automatic slip

compensation for almost constant speed at

varying loads. The speed control parameters

are set in parameter group PI-0# Speed PID

Control.

[1]

Speed

closed loop

Enables Speed closed loop control with feed-

back. Obtain full holding torque at 0 RPM.

For increased speed accuracy, provide a

feedback signal and set the speed PID

control. The speed control parameters are set

in parameter group PI-0# Speed PID Control.

[2]

Torque

Enables torque closed loop control with feed-

back. Only possible with “Flux with motor

feedback” option, H-41 Motor Control

Principle.

[3]

Process

Enables the use of process control in the

frequency converter. The process control

parameters are set in parameter groups PI-2#

and PI-3#.

[4]

Torque

open loop

Enables the use of torque open loop in Adv.

Vector Control mode (H-41 Motor Control

Principle). The torque PID parameters are set

in parameter group PI-1#.

[5]

Wobble

Enables the wobble functionality in

SF-00 Wobble Mode to SF-19 Wobble Delta

Freq. Scaled.

[6]

Surface

Winder

Enables the surface winder control specific

parameters in parameter group PI-2# and

PI-3#.

[7]

Extended

PID Speed

OL

Specific parameters in parameter group PI-2#

to PI-5#.

[8]

Extended

PID Speed

CL

Specific parameters in parameter group PI-2#

to PI-5#.

H-41 Motor Control Principle

Option:

Function:

NOTE

This parameter cannot be adjusted
while the motor is running.

Select which motor control principle to

employ.

H-41 Motor Control Principle

Option:

Function:

[0]

U/f

special motor mode, for parallel connected

motors in special motor applications. When

U/f is selected the characteristic of the

control principle can be edited in H-55 U/f

Characteristic - U and H-56 U/f Characteristic

- F.

[1]

*

Advanced

Vector

Control

Voltage Vector Control principle suitable for

most applications. The main benefit of

Advanced Vector Control operation is that it

uses a robust motor model.

[2]

Flux

sensorless

Flux Vector control without encoder

feedback, for simple installation and

robustness against sudden load changes.

[3]

Flux w/

motor feedb

very high accuracy speed and torque

control, suitable for the most demanding

applications.

The best shaft performance is normally achieved using
either of the two Flux Vector control modes [2] Flux
sensorless
and [3] Flux with encoder feedback.

H-42 Flux Motor Feedback Source

Option:

Function:

NOTE

This parameter cannot be adjusted
while the motor is running.

Select the interface at which to receive

feedback from the motor.

[0]

Motor feedback

par. H-42

[1]

*

24V encoder

A and B channel encoder, which can

be connected to the digital input

terminals 32/33 only. Terminals 32/33

must be programmed to No operation.

[2]

OPCENC

Encoder module option which can be

configured in parameter group EC-1#.

[3]

OPCRES

Optional resolver interface module

which can be configured in parameter

group RS-5#

[6]

Analog Input 53

[7]

Analog Input 54

[8]

Frequency input

29

[9]

Frequency input

33

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

63

3

3

Advertising