O-05 End-of-Timeout Function

Option:

Function:

Word Timeout Function is set to [7] Set-up 1,

[8] Set-up 2, [9]Set-up 3 or [10] Set-up 4.

[0]

Hold set-up

Retains the set-up selected in O-04 Control

Word Timeout Function and displays a

warning, until O-06 Reset Control Word

Timeout toggles. Then the frequency

converter resumes its original set-up.

[1]

*

Resume set-

up

Resumes the set-up active before the time-

out.

O-06 Reset Control Word Timeout

This parameter is active only when [0] Hold set-up has been

selected in O-05 End-of-Timeout Function.

Option:

Function:

[0]

*

Do not reset Retains the set-up specified in O-04 Control

Word Timeout Function, following a control

word time-out.

[1]

Do reset

Returns the frequency converter to the

original set-up following a control word time-

out. The frequency converter performs the

reset and then immediately reverts to the [0]

Do not reset setting

O-07 Diagnosis Trigger

Option:

Function:

This parameter enables and controls the

frequency converter diagnosis function and

permits expansion of the diagnosis data to 24

byte.

NOTE

This is only valid for Profibus.

[0] Disable: Do not send extended

diagnosis data even if they appear in

the frequency converter.

[1] Trigger on alarms: Send extended

diagnosis data when one or more

alarms appear in alarm DR-90 Alarm

Word or PB-53 Profibus Warning Word.

[2] Trigger alarms/warn.: Send extended

diagnosis data if one or more alarms or

warnings appear in alarm DR-90 Alarm

Word, PB-53 Profibus Warning Word, or

warning DR-92 Warning Word.

The content of the extended diagnosis frame is

as follows:

Byte

Content

Description

O-07 Diagnosis Trigger

Option:

Function:

0 - 5

Standard DP

Diagnose

Data

Standard DP Diagnose

Data

6

PDU length

xx

Header of extended

diagnostic data

7

Status type =

0x81

Header of extended

diagnostic data

8

Slot = 0

Header of extended

diagnostic data

9

Status info =

0

Header of extended

diagnostic data

10 - 13 DR-92 Warnin

g Word

14 - 17 DR-03 Status

Word

status word

18 - 21 DR-90 Alarm

Word

22 - 23 PB-53 Profibus

Warning Word

Communication

warning word

(Profibus)

Table 3.22

Enabling diagnosis may cause increased bus

traffic. Diagnosis functions are not supported by

all network types.

[0]

*

Disable

[1]

Trigger

on

alarms

[2]

Trigger

alarm/

warn.

O-08 Readout Filtering

If the speed feedback value readouts on fieldbus are fluctuating,

this function is used. Select filtered if the function is required. A

power-cycle is required for changes to take effect.

Option:

Function:

[0]

Motor Data Std-

Filt.

Select [0] for normal bus

readouts.

[1]

Motor Data LP-

Filter

Select [1] for filtered bus

readouts of the following

parameters:

DR-10 Power [kW]

DR-11 Power [hp]

DR-12 Motor Voltage

DR-14 Motor current

DR-16 Torque [Nm]

DR-17 Speed [RPM]

DR-22 Torque [%]

DR-25 Torque [Nm] High

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

87