H-47 Motor Angle Offset

Range:

Function:

This parameter is only active when P-20 Motor

Construction is set to [1] PM, non-salient SPM

(Permanent Magnet Motor).

H-48 Clockwise Direction

Option:

Function:

NOTE

This parameter cannot be adjusted while the
motor is running.

This parameter defines the term “Clockwise”

corresponding to the keypad direction arrow. Used

for easy change of direction of shaft rotation

without swapping motor wires.

[0]

*

Normal Motor shaft will turn in clockwise direction when

the frequency converter is connected U

⇒ U; V⇒V,

and W

⇒ W to motor.

[1]

Inverse Motor shaft will turn in counter clockwise direction

when the frequency converter is connected U

⇒U;

V

⇒V, and W⇒ W to motor.

3.7.4 H-5# Load Indep. Settings

Parameters to configure the load-independent motor
settings.

H-50 Motor Magnetisation at Zero Speed

Range:

Function:

100

%

*

[0 -

300

%]

Use this parameter along with H-51 Min Speed

Normal Magnetising [RPM] to obtain a different

thermal load on the motor when running at low

speed.

Enter a value which is a percentage of the rated

magnetizing current. If the setting is too low, the

torque on the motor shaft may be reduced.

Illustration 3.25 Motor Magnetisation

NOTE

H-50 Motor Magnetisation at Zero Speed will not have effect
when P-20 Motor Construction = [1] PM, non salient SPM.

H-51 Min Speed Normal Magnetising [RPM]

Range:

Function:

15 RPM

*

[10 - 300

RPM]

Set the required speed for normal

magnetising current. If the speed is set

lower than the motor slip speed,

H-50 Motor Magnetisation at Zero Speed

and H-51 Min Speed Normal Magnetising

[RPM] are of no significance.

Use this parameter along with H-50 Motor

Magnetisation at Zero Speed. See

Table 3.15.

NOTE

H-51 Min Speed Normal Magnetising [RPM] will not have
effect when P-20 Motor Construction = [1] PM, non salient
SPM.

H-52 Min Speed Normal Magnetising [Hz]

Range:

Function:

12.5 Hz

*

[0 - 250.0

Hz]

Set the required frequency for normal

magnetising current. If the frequency is set

lower than the motor slip frequency,

H-50 Motor Magnetisation at Zero Speed is

inactive.

Use this parameter along with H-50 Motor

Magnetisation at Zero Speed. See drawing

for H-50 Motor Magnetisation at Zero

Speed.

H-53 Model Shift Frequency

Range:

Function:

4.0

Hz

*

[4 -

18.0

Hz]

Flux Model shift

Enter the frequency value for shift between two

models for determining motor speed. Choose the

value based on settings in H-40 Configuration

Mode and H-41 Motor Control Principle. There are

two options: shift between Flux model 1 and Flux

model 2; or shift between Variable Current mode

and Flux model 2.

This parameter cannot be adjusted while the

motor is running.

Flux Model 1 – Flux model 2

This model is used when H-40 Configuration Mode

is set to [1] Speed closed loop or [2] Torque and

H-41 Motor Control Principle is set to [3] Flux w/

motor feedback. With this parameter it is possible

to make an adjustment of the shifting point

where AF-650 GP changes between Flux model 1

and Flux model 2, which is useful in some

sensitive speed and torque control applications.