20 terminal 54 low voltage, N-22 terminal 54 low current, 3 an-2# analog input 54 – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 74

Advertising
background image

AN-15 Terminal 53 High Ref./Feedb. Value

Range:

Function:

AN-13 Terminal 53 High

Current.

AN-16 Terminal 53 Filter Time Constant

Range:

Function:

0.001 s

*

[0.001 - 10

s]

NOTE

This parameter cannot be adjusted
while the motor is running.

Enter the time constant. This is a first-

order digital low pass filter time constant

for suppressing electrical noise in terminal

53. A high time constant value improves

dampening but also increases the time

delay through the filter.

3.8.3 AN-2# Analog Input 54

Parameters to configure the scaling and limits for Analog
Input 2 (terminal 54)

AN-20 Terminal 54 Low Voltage

Range:

Function:

0.07 V

*

[-10.00 - par.

AN-21 V]

Enter the low voltage value. This

analog input scaling value should

correspond to the minimum reference

value, set in F-52 Minimum Reference.

See also .

AN-21 Terminal 54 High Voltage

Range:

Function:

10 V

*

[par. AN-20 -

10 V]

Enter the high voltage value. This analog

input scaling value should correspond to

the high reference/feedback value set in

AN-25 Terminal 54 High Ref./Feedb. Value.

AN-22 Terminal 54 Low Current

Range:

Function:

0.14

mA

*

[0 - par.

AN-23 mA]

Enter the low current value. This

reference signal should correspond to the

minimum reference value, set in

F-52 Minimum Reference. The value must

be set at >2 mA in order to activate the

Live Zero Time-out Function in AN-01 Live

Zero Timeout Function.

AN-23 Terminal 54 High Current

Range:

Function:

20 mA

*

[par. AN-22 -

20 mA]

Enter the high current value

corresponding to the high reference/

feedback value set in AN-25 Terminal

54 High Ref./Feedb. Value.

AN-24 Terminal 54 Low Ref./Feedb. Value

Range:

Function:

0 ReferenceFeed-

backUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the analog

input scaling value

that corresponds to

the minimum

reference feedback

value set in

F-52 Minimum

Reference.

AN-25 Terminal 54 High Ref./Feedb. Value

Range:

Function:

1500.000 Referen-

ceFeedbackUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the analog

input scaling value

that corresponds to

the maximum

reference feedback

value set in

F-53 Maximum

Reference.

AN-26 Terminal 54 Filter Time Constant

Range:

Function:

0.001 s

*

[0.001 - 10

s]

NOTE

This parameter cannot be adjusted
while the motor is running.

Enter the time constant. This is a first-

order digital low pass filter time constant

for suppressing electrical noise in terminal

54. A high time constant value improves

dampening but also increases the time

delay through the filter.

3.8.4 AN-3# Analog Input X30/11

Parameters to configure the scaling and limits for Analog
Input 1 associated with OPCGPIO General Purpose Field
Installed Option Module.

AN-30 Terminal X30/11 Low Voltage

Range:

Function:

0.07 V

*

[0 - par. AN-31

V]

Sets the analog input scaling value to

correspond to the low reference/

feedback value (set in AN-34 Term.

X30/11 Low Ref./Feedb. Value).

AN-31 Terminal X30/11 High Voltage

Range:

Function:

10 V

*

[par. AN-30 - 10

V]

Sets the analog input scaling value to

correspond to the high reference/

feedback value (set in AN-35 Term.

X30/11 High Ref./Feedb. Value).

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

73