F-43 Current Limit

Range:

Function:

160.0

%

*

[1.0 -

1000.0 %]

This is a true current limit function that

continues in the oversynchronous range,

however due to field weakening the

motor torque at current limit will drop

accordingly when the voltage increase

stops above the synchronised speed of

the motor.

3.3.7 F-5# Extended References

Parameters to configure drive min/max reference and
reference function.

F-50 Reference Range

Option:

Function:

Select the range of the reference signal and the

feedback signal. Signal values can be positive

only, or positive and negative. The minimum

limit may have a negative value, unless [1] Speed

closed loop control or [3] Process is selected in

H-40 Configuration Mode.

[0]

Min -

Max

Select the range of the reference signal and the

feedback signal. Signal values can be positive

only, or positive and negative. The minimum

limit may have a negative value, unless [1] Speed

closed loop control or [3] Process is selected in

H-40 Configuration Mode.

[1]

*

-Max -

+Max

For both positive and negative values (both

directions, relative to H-08 Reverse Lock).

F-51 Reference/Feedback Unit

Option:

Function:

Select the unit to be used in Process PID Control

references and feedbacks. H-40 Configuration

Mode must be either [3] Process or [8] Extended

PID Control.

[0]

*

None

[1]

%

[2]

RPM

[3]

Hz

[4]

Nm

[5]

PPM

[10]

1/min

[12]

Pulse/s

[20]

l/s

[21]

l/min

[22]

l/h

[23]

m3/s

[24]

m3/min

[25]

m3/h

[30]

kg/s

[31]

kg/min

F-51 Reference/Feedback Unit

Option:

Function:

[32]

kg/h

[33]

t/min

[34]

t/h

[40]

m/s

[41]

m/min

[45]

m

[60]

°C

[70]

mbar

[71]

bar

[72]

Pa

[73]

kPa

[74]

m WG

[80]

kW

[120] GPM

[121] gal/s

[122] gal/min

[123] gal/h

[124] CFM

[125] ft3/s

[126] ft3/min

[127] ft3/h

[130] lb/s

[131] lb/min

[132] lb/h

[140] ft/s

[141] ft/min

[145] ft

[150] lb ft

[160] °F

[170] psi

[171] lb/in2

[172] in WG

[173] ft WG

[180] HP

F-52 Minimum Reference

Range:

Function:

0 Reference-

FeedbackUnit

*

[-999999.999 -

par. F-53

ReferenceFeed-

backUnit]

Enter the Minimum

Reference. The Minimum

Reference is the lowest

value obtainable by

summing all references.

Minimum Reference is active

only when F-50 Reference

Range is set to [0] Min.- Max.

The Minimum Reference

unit matches:

The choice of

configuration in

H-40 Configuration

Mode Configuration

Mode: for [1] Speed

Parameter Descriptions

AF-650 GP Programming Guide