H-83 precise stop function, 83 precise stop, Function – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 70: 81 min speed for function at stop, H-81 min speed, For function at stop [rpm

Advertising
background image

H-80 Function at Stop

Option:

Function:

solutions are available to pre-magnetize the

machine for the first start command:

1. Start the frequency converter

with a 0 RPM reference and wait 2

to 4 rotor time constants (see

below) before increasing the speed

reference.

2a. Set F-24 Holding Time to the

desired pre-mag time (2 to 4 rotor

time constants - see below).

2b. Set F-25 Start Function to either

[0] DC-hold or [1] DC-Brake.

Set the DC-hold or DC-brake

current magnitude (B-00 DC Hold

Current or B-01 DC Brake Current)

to be equal to I_pre-mag = Unom/

(1.73 x Xh)

Sample rotor time constants =

(Xh+X2)/(6.3*Freq_nom*Rr)

1 kW = 0.2 s

10 kW = 0.5 s

100 kW = 1.7 s

1000 kW = 2.5 s

[4]

DC Voltage

U0

When the motor is stopped, the H-55 U/f

Characteristic - U [0] parameter defines the

voltage at 0 Hz.

[5]

Coast at low

reference

When the reference is below H-81 Min Speed

for Function at Stop [RPM], the motor is

disconnected from the frequency converter.

[6]

Motor check,

alarm

H-81 Min Speed for Function at Stop [RPM]

Range:

Function:

3 RPM

*

[0 - 600 RPM] Set the speed at which to activate

H-80 Function at Stop.

H-82 Min Speed for Function at Stop [Hz]

Range:

Function:

0.1 Hz

*

[0 - 20.0 Hz] Set the output frequency at which to

activate H-80 Function at Stop.

H-83 Precise Stop Function

Option:

Function:

NOTE

This parameter cannot be adjusted while
the motor is running.

[0]

*

Precise

ramp

stop

Only optimal when the operational speed - of

e.g. the conveyor belt - is constant. This is an

H-83 Precise Stop Function

Option:

Function:

open loop control. Achieves high repetitive

precision at the stopping point.

[1]

Cnt stop

with reset

Counts the number of pulses, typically from an

encoder and generates a stop signal after a pre-

programmed number of pulses - H-84 Precise

Stop Counter Value - has been received at T29 or

T33 [30].

This is a direct feedback with one-way closed

loop control.

The counter function is activated (starts timing)

at the edge of the start signal (when it changes

from stop to start). After each precise stop the

number of pulses counted during decel to 0

RPM is reset.

[2]

Cnt stop

w/o reset

Same as [1] but the number of pulses counted

during decel to 0 rpm is deducted from the

counter value entered in H-84 Precise Stop

Counter Value.

This reset function can for example be used to

compensate for the extra distance done during

ramping down and to reduce the impacts of

gradual wear of mechanical parts.

[3]

Speed

comp

stop

Stops at precisely the same point, regardless of

the present speed, the stop signal is delayed

internally when the present speed is lower than

the maximum speed (set in F-03 Max Output

Frequency 1).

The delay is calculated on the basis of the

reference speed of the frequency converter and

not on the basis of the actual speed. Please

therefore make sure that the frequency

converter has ramped up before you activate

the speed compensated stop.

[4]

Com cnt

stop w/rst

Same as [3] but after each precise stop the

number of pulses counted during decel to 0

rpm is reset.

[5]

Comp cnt

stop w/o

r

Same as [3] but the number of pulses counted

during decel to 0 rpm is deducted from the

counter value entered in H-84 Precise Stop

Counter Value.

This reset function can for example be used to

compensate for the extra distance done during

ramping down and to reduce the impacts of

gradual wear of mechanical parts.

The Precise Stop Functions are advantageous in
applications where high precision is required.
If you use a standard stop command the accuracy is
determined by the internal task time. That is not the case
when using the precise stop function; it eliminates the task
time dependence and increases the accuracy substantially.
The frequency converter tolerance is normally given by its
task time. However, by using its special precise stop

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

69

3

3