Bit

Hex

Dec

Alarm Word

Alarm Word 2

Warning Word

Warning
Word 2

Extended
Status Word

7

00000080

128

Motor Th Over

(A11)

reserved

Motor Th Over (W11)

reserved

Output Current

High

8

00000100

256

Motor Electronic

OL Over (A10)

reserved

Motor Electronic OL

Over (W10)

reserved

Output Current Low

9

00000200

512

Drive Overld. (A9) reserved

Drive Overld (W9)

reserved

Output Freq High

10

00000400

1024

DC under Volt

(A8)

reserved

DC under Volt (W8)

Output Freq Low

11

00000800

2048

DC over Volt (A7) reserved

DC over Volt (W7)

Brake Check OK

12

00001000

4096

Short Circuit

(A16)

reserved

DC Voltage Low (W6)

reserved

Braking Max

13

00002000

8192

Inrush Fault (A33) reserved

DC Voltage High (W5)

Braking

14

00004000

16384

Mains ph. Loss

(A4)

reserved

Mains ph. Loss (W4)

Out of Speed Range

15

00008000

32768

Auto Tune Not

OK

reserved

No Motor (W3)

OVC Active

16

00010000

65536

Live Zero Error

(A2)

reserved

Live Zero Error (W2)

AC Brake

17

00020000

131072

Internal Fault

(A38)

KTY error

10V Low (W1)

KTY Warn

Password Timelock

18

00040000

262144

Brake Overload

(A26)

Fans error

Brake Overload (W26)

Fans Warn

Password Protection

19

00080000

524288

U phase Loss

(A30)

reserved

Brake Resistor (W25)

reserved

20

00100000

1048576

V phase Loss

(A31)

reserved

Brake IGBT (W27)

reserved

21

00200000

2097152

W phase Loss

(A32)

reserved

Speed Limit (W49)

reserved

22

00400000

4194304

Network Fault

(A34)

reserved

Network Fault (W34)

reserved

Unused

23

00800000

8388608

24 V Supply Low

(A47)

reserved

24V Supply Low (W47)

reserved

Unused

24

01000000

16777216

Mains Failure

(A36)

reserved

Mains Failure (W36)

reserved

Unused

25

02000000

33554432

1.8V Supply Low

(A48)

reserved

Current Limit (W59)

reserved

Unused

26

04000000

67108864

Brake Resistor

(A25)

reserved

Low Temp (W66)

reserved

Unused

27

08000000

134217728

Brake IGBT (A27)

reserved

Voltage Limit (W64)

reserved

Unused

28

10000000

268435456

Option Change

(A67)

reserved

Encoder loss (W90)

reserved

Unused

29

20000000

536870912

Drive Restored to

factory

settings(A80)

Feedback Fault

(A61, A90)

Feedback Fault (W61,

W90)

Unused

30

40000000

1073741824

Safe Stop (A68)

Safe Stop (A71)

Safe Stop (W68)

Safe Stop

(W71)

Unused

31

80000000

2147483648

Mech. brake low

(A63)

Dangerous

Failure (A72)

Extended Status Word

Unused

Table 5.3 Description of Alarm Word, Warning Word and Extended Status Word

The alarm words, warning words and extended status
words can be read out via serial bus or optional network
for diagnostics. See also DR-94 Ext. Status Word.