Historic log: event, Id-14 samples before trigger ) a, Samples before trigger ) – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 111: 3 id-2# historic log

Advertising
background image

ID-12 Trigger Event

Select the trigger event. When the trigger event occurs, a

window is applied to freeze the log. The log will then retain a

specified percentage of samples before the occurrence of the

trigger event (ID-14 Samples Before Trigger).

Choices are described under E-## Digital Output.

Option:

Function:

[14]

Below feedb. low

[15]

Above feedb. high

[16]

Thermal warning

[17]

Line voltage out of range

[18]

Reversing

[19]

Warning

[20]

Alarm (trip)

[21]

Alarm (trip lock)

[22]

Comparator 0

[23]

Comparator 1

[24]

Comparator 2

[25]

Comparator 3

[26]

Logic rule 0

[27]

Logic rule 1

[28]

Logic rule 2

[29]

Logic rule 3

[33]

Digital input DI18

[34]

Digital input DI19

[35]

Digital input DI27

[36]

Digital input DI29

[37]

Digital input DI32

[38]

Digital input DI33

[50]

Comparator 4

[51]

Comparator 5

[60]

Logic rule 4

[61]

Logic rule 5

ID-13 Trending Mode

Option:

Function:

[0]

*

Trend always

Select [0] Log always for continuous

logging.

[1]

Trend once on

trigger

Select [1] Log once on trigger to

conditionally start and stop logging using

ID-12 Trigger Event and ID-14 Samples

Before Trigger.

ID-14 Samples Before Trigger

Range:

Function:

50

*

[0 - 100] Enter the percentage of all samples prior to a

trigger event which are to be retained in the log.

See also ID-12 Trigger Event and ID-13 Trending

Mode.

3.17.3 ID-2# Historic Log

View up to 50 data items logged up to the last reported
trip. The data is stored in array parameters, where [0] is the
most recent data and [49] is the oldest data.

ID-20 Historic Log: Event

Array [50]

Range:

Function:

0

*

[0 - 255]

View the event type of the logged events.

ID-21 Historic Log: Value

Array [50]

Range:

Function:

0

*

[0 -

2147483647]

View the value of the logged event.

Interpret the event values according to this

table:

Digtal input

Decimal value. See

DR-60 Digital Input for

description after

converting to binary

value.

Digital output

Decimal value. See

DR-66 Digital Output [bin]

for description after

converting to binary

value.

Warning word

Decimal value. See

DR-92 Warning Word for

description.

Alarm word

Decimal value. See

DR-90 Alarm Word for

description.

Status word

Decimal value. See

DR-03 Status Word for

description after

converting to binary

value.

Control word

Decimal value. See

DR-00 Control Word for

description.

Extended

status word

Decimal value. See

DR-94 Ext. Status Word for

description.

Table 3.29

Parameter Descriptions

AF-650 GP Programming Guide

110

DET-618C

3

3

Advertising