E-27 Off Delay, Relay

Array[2]: Relay1[0], Relay2[1]

Range:

Function:

0.01 s

*

[0.01 - 600 s] Enter the delay of the relay cut-out time.

Select one of available mechanical relays

and OPCRLY Relay Option Module in an

array function. See E-24 Function Relay.

Illustration 3.17 Off Delay, Relay

If the selected Event condition changes before the on- or
off delay timer expires, the relay output is unaffected.

E-51 Terminal 27 Mode

Option:

Function:

NOTE

This parameter cannot be adjusted while the
motor is running.

[0]

*

Input

Defines terminal 27 as a digital input.

[1]

Output Defines terminal 27 as a digital output.

E-52 Terminal 29 Mode

Option:

Function:

[0]

*

Input

Defines terminal 29 as a digital input.

[1]

Output

Defines terminal 29 as a digital output.

E-53 Terminal X30/2 Digital Input

Option: Function:

The options are the same as listed for parameter group

E-0#.

E-54 Terminal X30/3 Digital Input

Option: Function:

The options are the same as listed for parameter group

E-0#.

E-55 Terminal X30/4 Digital Input

Option: Function:

The options are the same as listed for parameter group

E-0#.

E-56 Term X30/6 Digi Out (OPCGPIO)

This parameter is active when OPCGPIO General Purpose I/O

Option Module is mounted in the frequency converter. Functions

are described under E-2# Digital Outputs.

E-57 Term X30/7 Digi Out (OPCGPIO)

This parameter is active when OPCGPIO General Purpose I/O

Option Module is mounted in the frequency converter. Functions

are described under E-2# Digital Outputs.

3.4.4 E-6# Pulse Input

Parameters to configure terminal 29 and 33 as Pulse Train
inputs.

E-60 Term. 29 Low Frequency

Range:

Function:

100 Hz

*

[0 - 110000

Hz]

Enter the low frequency limit

corresponding to the low motor shaft

speed (i.e. low reference value) in

E-62 Term. 29 Low Ref./Feedb. Value.

Refer to the diagram in this section.

E-61 Term. 29 High Frequency

Range:

Function:

100 Hz

*

[0 - 110000

Hz]

Enter the high frequency limit

corresponding to the high motor shaft

speed (i.e. high reference value) in

E-63 Term. 29 High Ref./Feedb. Value..

E-62 Term. 29 Low Ref./Feedb. Value

Range:

Function:

0 ReferenceFeed-

backUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the low reference

value limit for the motor

shaft speed [RPM]. This

is also the lowest

feedback value, see also

E-67 Term. 33 Low Ref./

Feedb. Value. Set

terminal 29 to digital

input (E-52 Terminal 29

Mode = [0] input

(default) and

E-04 Terminal 29 Digital

Input = applicable

value).

E-63 Term. 29 High Ref./Feedb. Value

Range:

Function:

1500.000 Referen-

ceFeedbackUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the high reference

value [RPM] for the

motor shaft speed and

the high feedback value,

see also E-68 Term. 33

High Ref./Feedb. Value.